Cooling, Heating (except during defrosting operation) – Sanyo STB1220C1 User Manual

Page 48

Advertising
background image

44

Cooling

Once the compressor stops, it will not start running again for about 3 minutes.

Thermo. ON : When the room temperature rises above T + 1°F (T°F is set temperature).

Compressor

ON

Thermo. OFF : When the room temperature falls below set temperature T°F.

Compressor

OFF

Heating (Except during defrosting operation)

Once the compressor stops, it will not start running again for about 3 minutes.

Thermo. ON : When the room temperature falls below T°F (T°F is set temperature).

Compressor

ON

Thermo. OFF : When the room temperature rises above T + 1°F.

Compressor

OFF

Changeover to Heater ON : When the room temperature falls below T – 4°F, the unit turns off heat pump

operation and electric heater comes on instead of compressor.

Changeover to Heat pump : When the room temperature rises above T – 3°F, the unit resumes heat pump

operation and compressor comes on instead of electric heater.

ON

ON

ON

ON

ON

ON

ON

ON

3 minutes

or more

T

°

F

T–3

°

F

T+1

°

F

T–4

°

F

set temp.

Compressor

Heater

3 minutes

3 minutes

Room temp.

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

T

°

F

T+1

°

F

set temp.

Compressor

3 minutes

or more

3 minutes

Room temp.

OFF

OFF

Heat Pump Model

Model STB0823H1