6 connection, 1 overview of connection, Connection – Siemens Plant Central Clock TC100 User Manual

Page 34: Overview of connection, Connection (chapter 6)

Advertising
background image

6-3



©

Siemens AG 2010 All Rights Reserved

SICLOCK

®

TC100 Operating Instructions

Connection

6

6.1

Overview of connection

Ensure that the installation complies with the following conditions:

•

The device may only be connected to 24 VDC power supply systems which
meet the requirements of a safe extra-low voltage with protective separation
according to SELV. The conductor cross-section selected must be large
enough so that if there is a short circuit in the SICLOCK TC100 no damage
can be caused by an overheated cable. For the conductor cross-section, see
Connecting the power supply (Chapter 6.2).

•

Avoid extreme ambient conditions as far as possible.

•

Protect the device against dust, moisture, heat and severe vibrations.

•

Do not place the device in direct sunlight.

•

Install the device in such a way that it cannot pose any danger, for example by
falling down.

•

Do not cover the ventilation slots

•

Permissible mounting position (Chapter 4.4.2).

Notice

Only connect peripheral devices suitable for an industrial environment.

Caution

Strictly adhere to the specifications for peripheral equipment.