13 technical data, Technical data – Siemens Plant Central Clock TC100 User Manual

Page 98

Advertising
background image

13-9



©

Siemens AG 2010 All Rights Reserved

Operating Instructions SICLOCK

®

TC100

Technical data

13

Table 13-1

SICLOCK TC100, technical data

Dimensions

180.0 x 88.9 x 47.0 (W x H x D in mm)

Weight

approx. 750 g

Supply voltage

24 VDC (-15% to +20%) at X1

Power supply

continuous current 0.7 A max.

Transient voltage interruption

3 ms (at 20.4 to 28.8 V) max.

Power consumption

15 W max.

Power loss

typically 7.5 W

External fuse

1 A slow-action

Degree of protection

IP 20

Mounting type

35 mm standard mounting rail
EN 50022-35 mounting rail (15 mm high) or
SIMATIC DIN rail

Safety

Product standard

EN 61131-2 (environment)

Test voltage

Circuits with nominal voltage Ue <50 V relative to other circuits or
ground, test voltage 500 VDC:

Protection class

Protection class III according to EN 60536

Electrical safety

EN 60950-1

Time of day characteristics

Accuracy in relation to
GPS signal

< 50 µs

Accuracy in relation to
DCF77 signal

< 1000 µs

Accuracy in case of loss of
GPS signal

< 50x10

-9

Accuracy in case of loss of
DCF77 signal

< 1x10

-6

Accuracy in case of power
failure

< 4x10

-6

Time-of-day correction by
microsteps

< 50 µs/s

Jitter in GPS operation

< 200 ns/s

Reserve power

See battery

Advertising