2. Installation

Initiating Device Circuits

18

PDRP-1002 Instruction Manual PN 51135:B0 04/06/01

Initiating Device Circuits

The control panel provides two Initiating Device Circuits (#1 and #2) and they may be configured as either
Style D (Class A) or Style B (Class B). Circuit #3 is designated as an Abort Switch Circuit and Circuit #4
is a Manual Release Circuit.

Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and
Waterflow alarm devices.

Note: Refer to "Appendix B: Compatible Devices" on page 41 for compatible devices.

• Wire all alarm initiating devices sequentially for proper supervision.

• Observe polarity when connecting polarized devices.

• All circuits are supervised and power-limited.

• Leave dummy load resistor (provided) on all unused circuits.

Figure 7 Initiating Device Circuits

Style D (Class A)

Initiating Device

Circuit

Style B (Class B)

Initiating Device

Circuit

4.7K, 1/2-Watt resistor
PN 71252 (UL listed)

Style B (Class B)

Abort Switch

Circuit

Two-wire
Smoke
Detector

Manual
Pull Station

Heat
Detector

Style B (Class B)

Manual Release

Circuit

M

R

P

44-

idc.cdr

Note: Silk screen printing on circuit board moved to bottom for clarity