Setting mode of operation, Dip switch functions, Switch #1 - cross zone – System Sensor PDRP-1002 Series User Manual

Page 28: Off on

Advertising
background image

2. Installation

Setting Mode of Operation

28

PDRP-1002 Instruction Manual PN 51135:B0 04/06/01

Setting Mode of Operation

Select operating mode by setting the SW1 DIP switches as described below; basic programming options
are shown in this section.

After any changes are made to the configuration of the switches, the panel must be reset.

For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 36.

Figure 19 DIP Switch Settings

DIP Switch Functions

Switch #1 - Cross Zone

Select the desired mode of operation and set switch per appropriate column:

OFF

ON

NAC #1

Activated by an alarm in either
IDC # 1 or IDC #2.

NAC #1

Pre-discharge Alarm - Activated by
the first alarmed zone in the system.
Initiation of an alarm on the other
zone will shut this output off

NAC #2

Activated by an alarm in either
IDC #1 or IDC #2.

Note: The NAC will pulse at 60 ppm
while timer is running or frozen by
abort and will sound steady upon
release (time out).

NAC #2

Activated when alarms occur on
both IDC #1 or IDC #2.

Note: The NAC will pulse at 60 ppm
while timer is running or frozen by
abort and will sound steady upon
release (time out).

REL #1
REL #2

Will be activated when the timer expires (provided that REL #2 is functioning as a
releasing circuit - set via DIP switch #2)

The Releasing Circuit Delay Timer will start
whenever an alarm occurs on either IDC #1 or
IDC #2.

The Releasing Circuit Delay Timer will start
whenever an alarm occurs on both IDC #1 or
IDC #2.

S W 1

MS

44-d

ipsw

.cdr

Basic Programming

Switch 1: Cross Zone

Switch 2: Supervisory

Abort Options

Switch 3: Delay Timer
Switch 4: Delay Timer

Delay Timer
Switch 5: Abort Option
Switch 6: Abort Option