Setting Mode of Operation

30

PDRP-1002 Instruction Manual PN 51135:B0 04/06/01

Zone Relay Module Configuration

Relay #1, #2, #3 and #4 of the the 4XZM Zone Relay Module have specific functions based on the
configuration of DIP Switches #1 and #2 on the control panel. The table below provides a description of
these functions.

DIP #1 is OFF

(Either Zone)

DIP #1 is ON

(Cross Zone)\

DIP #2 is ON (Supervisory)

Either Zone

Cross Zone

Relay #1

Activate when alarm

is detected in

Zone #1 or Zone #2

Activates when first

alarm is detected in

the system

Same

Same

Relay #2

Activates upon

second alarm

Same

Relay #3

Activates when

Release 1 is activated

Activates when

Release 1 is activated

Same

Same

Relay #4

Activates when

Release 2 is activated

Activates when

Release 2 is activated

Not Used

Not Used

Note: Relay #5 is reserved for General Alarm and Relay #6 is reserved for System Trouble.