System Sensor DH400ACDCP User Manual

Page 2

Advertising
background image

[3] Contents Of The Duct Detector Kit
1. Complete housing base and cover assembly
2. Two #10 sheet metal mounting screws
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two

5

/

16

˝ O-rings

7. Two rubber tube bushing seals
8. Four #6 self-tapping mounting screws for the sampling

and optional exhaust tube extension

9. One filter adapter
10. One inlet tube end plug
11. Two #10 speed nuts
NOTE: The inlet sampling tube must be ordered separately.
It must be the correct length for the width of the duct where
it will be installed. See Table 1 on page 4 to determine the
inlet tube required for different duct widths.
[4] Limitations Of Duct Detectors

WARNING

The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUB-
STITUTE FOR OPEN AREA DETECTOR PROTECTION as a
means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.

System Sensor supports this position and strongly recom-
mends that the user read NFPA Standards 90A, 72, and 101.
The DH400ACDCP Air Duct Smoke Detectors are listed per
UL 268A.

WARNING

This device will not operate without electrical power.
Frequently, fire situations may cause an interruption of
power. The system safeguards should be discussed with
your local fire protection specialist.

WARNING

This device does not sense smoke unless the ventilation
system is operating.

CAUTION

For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be protected from the elements and op-
erated within ALL electrical and environmental specifica-
tions listed in this manual. Failure to comply with these
requirements may prevent the detector from activating
when smoke is present in the air duct.

[5] Installation Sequence
Step

Page

[5.1] Verify duct air flow direction and velocity

3

[5.2] Drill the mounting holes

3

[5.3] Secure the detector housing to the duct

3

[5.4] Install the sampling tube

3

[5.5] Complete the field wiring

5

[5.6] Install the filters and check pressure differential

5

[5.7] Perform detector check

5

[5.8] Install the cover

5

D400-13-00

2

I56-0555-010R

[2] Figure 1. Exploded view of ductdetector components:

H0529-00

SAMPLING TUBE

FILTERS

CONDUIT HOLES

DUCT DETECTOR

HOUSING

TERMINAL STRIP

PC BOARD

INSULATOR

DUCT DETECTOR

COVER

SAMPLING TUBE

MOUNTING

SCREWS

DETECTOR HEAD

EXHAUST

FILTER ADAPTER

DETECTOR BASE

INLET SAMPLING TUBE

(SUPPLIED SEPARATELY)

O-RINGS

FOAM

GASKETS

HOUSING

MOUNTING SCREWS

TEST MAGNET

TUBE

END

PLUG

Advertising