System Sensor DH400ACDCP User Manual

Page 7

Advertising
background image

24V

120

VAC

220/240

VAC

1

2

12

13

14

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

15

16

17

18

19

20

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

ALARM INITIATION CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS

REMOVED, AND DURING RESET. OPEN CONTACTS

SIGNAL TROUBLE CONDITION TO PANEL.

9

8

5

(+) ALARM SIGNAL

AUDIBLE PIEZO ALERT WITH ALARM AND

POWER (TROUBLE) LEDS. FOR STAND ALONE

APPLICATIONS ONLY. APA451 RECOMMENDED

FOR COMPLIANCE TO NFPA 90A. LOCATE IN

NORMALLY OCCUPIED AREA OF PREMISES.

DH400ACDCP

DUCT DETECTOR

SEE SPECIFICATIONS FOR

ADDITIONAL POWER

SUPPLY INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER’S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

TROUBLE CONTACT RATING

0.3A @ 32 VAC/DC

POWER INPUTS ACCEPT

24 VDC, 24 VAC 50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.

ALARM AUXILIARY CONTACT RATINGS

10A @ 30 VDC

10A @ 250 VAC

500mA MINIMUM @ 24 VDC

NOT INTENDED FOR CONNECTION

TO CONTROL PANELS.

ALARM INITIATION CONTACT RATING

2.0A @ 30 VAC/DC (0.6 POWER FACTOR)

TROUBLE CONTACTS CLOSED IN STANDBY AND ALARM.

CONTACTS OPEN WHILE DETECTOR HEAD OR POWER

IS REMOVED, AND DURING RESET. OPEN CONTACTS

EXTINGUISH OPTIONAL APA451 GREEN “POWER” LED

TO INDICATE TROUBLE CONDITION.

(–) AUX POWER

(+) AUX POWER

TROUBLE

CONTACTS

APA451

N.O.

6

7

10

11

COMMON

FIELD

INSTALLED

JUMPER

POWER

3

GRN.

RED

1

2 ALARM

H0253-00

Figure 8. Wiring diagram for duct detector systems equipped without a control panel (see Figure 9 for wiring
of additional optional accessories):

D400-13-00

7

I56-0555-010R