Model 4501-XX Toxic Gas Sensor Module

Page 6 of 35

4. INSTALLATION

4.1 SENSOR MODULE LOCATIONS

The gas sensor module utilizes a diffusion type sensor which
should be located close to either the expected source or
destination of the gas hazard. If the gas is heavier than air, the
sensor module should be installed within 24 inches of the ground
or floor. If it is lighter than air, move it above 6’.

After optimum locations are determined based on the above
recommendations, consideration should be given to placing the
sensor modules in locations which are accessible for calibration
service. Slight adjustments to the location of the sensor module
may have little impact on effectiveness but major effect on
accessibility.

• Modules should be placed in areas accessible for

calibration.

• The cover should face out from the wall for easy access.
• Sensors should be pointed down and the conduit should

include an inverse trap to reduce moisture (condensation)
from accumulating in the electronics enclosure.

Model Gas

Specific

Gravity

N/A Air

1.00

4501-04 CO 0.97

4501-05 H

2

S 1.19

4501-06 Cl

2

2.49

4501-08 ClO

2

3.09

4501-10 SO

2

2.26

4501-12 NO

2

1.59

4501-25 NH

3

0.60

4501-26 HF 1.86

Table 4 - 1: Specific Gravities