Make the electrical connections – usa – Kohler 120V Bath with Airjets 1198326-2-A User Manual

Page 7

Advertising
background image

3. Make the Electrical Connections – USA

WARNING: Risk of electric shock.

Make sure the power has been disconnected before performing

the following procedures.

WARNING: Risk of electric shock.

Connect the blower motor to a properly grounded,

grounding-type receptacle protected by a Ground-Fault Circuit-Interrupter (GFCI) or Residual
Current Device (RCD). Do not remove the grounding pin from the plug. Do not use a grounding
adapter.

NOTICE:

The blower motor is equipped with a cord and plug. A qualified electrician must install a GFCI-

or RCD-protected, 120 V, 15 A, grounded outlet for the blower. No other load should be on this circuit.

Install an electrical outlet behind the bath, at least 1-1/2

″ (38 mm) above the subfloor, and within

reach of the 24

″ (610 mm) power cord.

Plug the blower into this outlet.

Install a GFCI-protected
120 V, 15 A grounded outlet.

Bond in accordance
with applicable codes.

Air Intake

24" (610 mm) Max. Distance
Between Blower and Outlet

Kohler Co.

7

1198326-2-A