Lennox International Inc. MPB35ST-NM User Manual
Page 5
 
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
Millivolt appliances are fi tted with an OFF/ON 
Rocker Switch located behind the control 
compartment access panel, below the appli-
ance front glass enclosure panel (see Figure 1 
for location). Once the pilot is lit, the OFF/ON 
rocker switch will control the appliance OFF/ON 
burner operation. To operate: Toggle the switch 
between its ON and OFF positions.
If your millivolt appliance is equipped with an 
optional remote switch kit (wall switch or remote 
control) and the pilot is lit, the appliance main 
burner may be turned on and off using the 
optional switch. When using an optional remote 
switch, turn off the standard OFF/ON switch.
Note: To prevent excessive resistance in burner 
circuit (which can cause burner operation prob-
lems), only one burner control switch should be 
wired to valve. Therefore, if an optional control 
switch is installed, the standard Off/On switch 
and wires should be removed.
Electronic Appliances -
To light electronic appliances refer to the 
detailed lighting instructions found on  Pagex 
19. Electronic appliance lighting instructions 
may also be found on the pull out lighting instruc-
tion labels attached to the gas control valve. 
Once the pilot is lit, if your electronic appliance 
is equipped with an optional burner control 
switch kit the appliance main burner may be 
turned on and off using the optional switch 
(See Optional Accessories on Pagex 15 - wall 
switch, or remote control Receiver). 
Figure 3
Honeywell Electronic Gas Valve
F
F
O
NI
P
S
I
N
O
L
O
R
T
N
O
C
GI
N
TI
ER
Manifold
Pressure
Port
ON / OFF Switch
Inlet 
Pressure
Port
Electronic Gas 
Control Valve
2. During the fi rst initial burns of these appli-
ances, there will be some odor emitted (see 
Burn-In Period on Page 3 ). 
3. Keep the lower control compartment clean
by vacuuming or brushing at least twice a 
year. More frequent cleaning may be required 
due to excessive lint from carpeting, bedding 
materials, pet hair, etc. It is very important 
that the control compartments, burners 
and circulating air passageways of the 
appliance are kept clean.
4. Always turn off gas to the pilot (millivolt
appliances) and let the appliance cool down 
before cleaning. Before re-lighting, refer 
to the lighting instructions in this manual. 
Lighting instructions may also be found 
on the pull out lighting instruction labels 
attached to the gas control valve. 
5. Always keep the appliance area clear and
free from combustible materials, gasoline 
and other fl ammable liquids.
6. Remember, Millivolt appliances have a con-
tinuous burning pilot fl ame. Exercise cau-
tion when using products with combustible 
vapors.
VENT OPERATION TEST
A vent operation test is required as part of the 
installation to verify that proper venting condi-
tions exist and should be done periodically to 
ensure nothing has changed that would affect 
proper venting of the appliance.
Procedure:
1. ENSURE APPLIANCE IS OFF (PILOT ONLY) 
AND COOL.
2. Open both latches on one of the glass
enclosure doors and slightly prop it open at 
the bottom (approx. 1/4” gap). See Figure 
6 on Page 9. 
3. Turn on all the exhaust fans in the dwelling
(and any other appliances which remove 
air from the dwelling, such as a furnace or 
clothes dryer, etc.). 
4. Ensure that all the doors and windows in
the room where the fi replace is located are 
closed.
5. Light the appliance (see Lighting Instruc-
tions, Pages 18 & 19 ). Adjust fl ame 
height to highest setting and operate for 
approximately 5-10 minutes. Do not leave 
appliance unattended.
6. Take a smoke producing device and move it
along the bottom edge of the glass door (where 
it is cracked open). If smoke is drawn into the 
fi rebox, the vent operation is adequate. 
IF THE SMOKE IS NOT DRAWN INTO
THE FIREBOX, TURN THE APPLIANCE 
OFF AND CALL A QUALIFIED SERVICE 
TECHNICIAN.
Variable Flame Height Adjustment 
( Millivolt Appliances only) 
1. All Millivolt appliances are equipped with a
variable gas control valve. Flame height for 
these models may be adjusted through a 
range between fi xed low and high settings 
while the appliance is in operation. Adjust 
the fl ame height as desired after lighting the 
appliance by rotating the variable adjustment 
control knob (HI/LO) located on the front of 
the valve (refer to Figure 2 ). 
SPILL SWITCH OPERATION
Manual-Reset (safety limit) Spill Switch
This appliance is equipped with a (safety limit) 
spill switch that is designed to "trip" and discon-
nect the burner circuit if fl ue spillage occurs 
(because of improper venting of combustion 
products or vent blockage). If, during appliance 
operation, the burner fl ame goes out (indepen-
dently of the burner OFF/ON wall switch), it may 
be due to the operation of this (safety limit) spill 
switch. If this switch "trips" it will need to be 
manually reset by pressing the reset button on 
switch (see Figure 4 ).
Procedure to Reset (safety limit) Spill Switch
ALLOW APPLIANCE TO COOL COMPLETELY 
BEFORE ACCESSING AND RESETTING
To access the spill switch:
1. Pull off the top louvered panel.
2. Locate and press the red reset button on 
the switch (it will click & lock in).
The appliance should then relight and remain 
lit. If this does not occur, turn off the appliance 
and call a qualifi ed service technician.
Press Reset Button on 
Spill Switch
Remove Top 
Louvered 
Panel (or 
optional 
radiant panel, 
if applicable)
Figure 4 - Spill Switch