LG SHADOWDANCE LSVFSD-LP User Manual

Page 5

Advertising
background image

Note: Diagrams aND illustratioNs are Not to scale.

5

this heater shall not be installed in a confined space or unusually tight

construction unless provisions are provided for adequate combustion

and ventilation air. the heater may be located in unusually tight construc-

tion provided the space is unconfined, or if confined, is provided with two

permanent openings communicating directly with an additional room(s)

of sufficient volume so that the combined volume of all connected spaces

meets the criteria for an unconfined space, (National Fuel gas code aNsi

Z.1 (latest edition), section 5.). generally 50 ft



per 1,000 Btu input

of all operating appliances in the space.
the National Fuel gas code, aNsi Z.1/NFPa 54-latest edition defines

a confined space as a space whose volume is less than 50 cubic feet per

1000 Btu per hour (4.8 m³ per kw) of the aggregate input rating of all

appliances installed in that space and an unconfined space as a space

whose volume is not less than 50 cubic feet per 1000 Btu per hour (4.8

m³ per kw) of the aggregate input rating of all appliances installed in

that space. rooms communicating directly with the space in which the

appliances are installed, through openings not furnished with doors, are

considered a part of the unconfined space.
rooms communicating directly with the space in which the appliances

are installed, through openings not furnished with doors, are considered

a part of the unconfined space.
unusually tight construction is defined as construction where:

a. Wall and ceilings exposed to the outside atmosphere have a continu-

ous water vapor retarder with a rating or one perm (6 x 1011 kg per

pa-sec-m) or less with openings gasketed or sealed, and

b. Weather stripping has been added on operable windows and doors,

and

c. caulking or sealants are applied to areas such as joints around window

and door frames, between sole plates and floors, between wall-ceiling

joints, between wall panels, at penetrations for plumbing, electrical,

and gas lines, and at other openings.

use the following equations to determine if you have a confined or

unconfined space.
1. Determine the volume of space — ft



.

length x Width x Height = _____ ft



(include adjoining rooms with doorless passageways or ventilation grills

between rooms).

Example: 4' (l) x 16' (W) x 8' (H) = 07 ft



2. Divide the volume of space by 50 ft



to determine the maximum Btu/Hr

the space can support.

(volume of space – ft



)/ 50 ft



= (maximum Btu/Hr the space can

support)

Example: 07 ft



/ 50 ft



= 61.44

or 61,440 Btu/Hr the space can support.
3. add the Btu/Hr of all the fuel burning appliances in the space.
Vent-Free Heater

________ Btu/Hr

gas appliance #1*

________ Btu/Hr

gas appliance #

+________ Btu/Hr

total =________ Btu/Hr

Example:

Vent-Free Heater

6,000 Btu/Hr

gas appliance #1

5,000 Btu/Hr

(water heater)

total = 71,000 Btu/Hr

* Do not include Direct-Vent gas appliances. Direct-Vent is sealed

combustion and draws combustion air from the outdoors.

Requirements for the Commonwealth of Massachusetts

Note: The following requirements reference various Massachusetts

and national codes not contained in this document.
un-vented room Heaters shall be installed in accordance with 57 cmr

0.00 and 48 cmr .00 through 7.00:
(a) Permits and inspections: in addition to complying with 48 cmr

.05 the following requirements must be satisfied:

1. a permit shall be obtained from the head of the fire department and

the local or state gas inspector having jurisdiction for the installation

of all unvented propane or natural gas-fired space/room heaters.

. the permits shall be conditioned upon final inspection and approval

of installation by the head of the fire department and the local or state

gas inspector having jurisdiction.

. a copy of the manufacturer’s installation/operating literature shall be

submitted with each permit application.

4. Before operation, the Head of the Fire Department and the local or

state gas inspector shall inspect the installation for compliance with

57 cmr (Board of Fire Prevention regulations) and 48 cmr (Board

of state examiners of Plumbers and gas Fitters).

5. a final inspection by the state or local gas inspector of the unvented

space/room heater shall not be performed until proof is provided

that the head of the fire department having jurisdiction has granted

a permit.

(b)unvented propane or natural gas-fired space/room heaters

shall conform to aNsi Z1.11., be equipped with an oxygen

depletion safety (oDs) shutoff system and be Product-approved

in accordance with 48 cmr.

(c)unvented propane or natural gas-fired space/room heaters

shall be installed in accordance with their listings and the

manufacturer’s instructions. Proper clearances to combustibles

shall be maintained. in no case shall the clearances be such as

to interfere with combustion air and accessibility.

(d)installations shall be of a permanent type, with a permanently

piped fuel supply in accordance with 48 cmr. lPg appliances

shall be subject to the storage requirements in accordance with

57 cmr 6.00. Portable unvented propane or natural gas-fired

space/room heaters shall be prohibited.

(e)unvented propane or natural gas-fired space/room heaters shall

be prohibited in bedrooms and bathrooms.

(f)space/room heaters shall be properly sized for the room or space

of installation, but shall not exceed a maximum of 40,000 Btu

input per room or space.

(g)in occupancies with an unvented propane or natural gas-fired

space/room heater, no less than one listed carbon monoxide

detector that is installed in accordance with the manufacturers

instructions shall be installed and maintained near the space

where the heater is located.

1. any building wherein the heater is to be installed shall,

as a precondition to such installation, have working smoke

detectors installed and maintained in accordance with the

requirements of 780 cmr (state Board of Building regulations

and standards) in effect at the time of construction or;

. if no requirement was in effect at the time of construc-

tion the smoke detector shall be compliant and installed as

provided for in m.g.l. c. 148, § 6e.

(h)in rooms and buildings served by an unvented propane or

natural gas-fired space/room heater, a primary source of heat,

which is operable, shall be permanently installed and maintained

in the building in accordance with 105 cmr (Department of

Public Health).

(i)sellers of unvented propane or natural gas-fired space/room

heaters shall provide to each purchaser a copy of 57 cmr

0.00 upon sale of the unit.

• installation and repair must be done by a plumber or gas fitter licensed

in the commonwealth of massachusetts.

• the flexible gas line connector used shall not exceed 6 inches (9

centimeters) in length.

• the individual manual shut-off must be a t-handle type valve.

COMBUSTION AND VENTILATION AIR

Advertising