TROUBLESHOOTING

Problem

Cause

Solution

MAINS lamp (orange) not

illuminated.

Mains not present.

Call qualified service personnel to restore

power to socket.

2U POD input cord not

connected to mains.

Refer to 2U POD installation instructions in

this manual:

Installation on GXT 2U UPS and

Rack Mount Installation.

UPS Available lamp (green) not

illuminated.

UPS output power not

present.

Turn on UPS. Refer to UPS user manual.

UPS input and/or output cord

not connected to 2U POD.

Refer to 2U POD installation instructions in

this manual:

Installation on GXT 2U UPS and

Rack Mount Installation.

2U POD will not start some / all

connected loads.

2U POD output circuit

breaker has tripped.

Reset 2U POD circuit protectors.

2U POD circuit protectors trip

after resetting.

Overcurrent on 2U POD

socket.

Recalculate load requirements, distribute

load among other 2U POD sockets.