115v specifications – Liebert PowerSure Personal User Manual

Page 10

Advertising
background image

10


115V SPECIFICATIONS

Model Number

PSP300-115

PSP500-115

Model Rating VA / W

300 / 180

500 / 300

DIMENSIONS: in (mm)

Unit H x W x D

7.0 x 3.0 x 9.4

(178 x 76 x 238)

7.0 x 3.0 x 9.4

(178 x 76 x 238)

Shipping H x W x D

10.6 x 4.3 x 12.3

(270 x 110 x 312)

10.6 x 4.3 x 12.3

(270 x 110 x 312)

WEIGHT: lbs (kg)

Unit

6.2 (2.8)

8.0 (3.6)

Shipping

7.7 (3.5)

9.5 (4.3)

INPUT AC PARAMETERS

Voltage Range
without Battery Operation

90-132 VAC

Low Line Transfer

90 VAC

High Line Transfer

132 VAC

Frequency

45-55 Hz or 54-66 Hz; auto sensing

Input Power Cord

6 ft. detachable, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

Output Receptacles

(4) 5-15R

Voltage (Battery Mode)

115 VAC + 5%

Output Current

2.6 A

4.3 A

Waveform (Battery Mode)

Stepped Sinewave

Frequency

50 Hz or 60 Hz; auto sensing

Overload Warning
(Utility and Battery Modes)

101 – 120%

Overload Shutdown
(Utility and Battery Modes)

Overload Warning

+ (15 – 25 W)

Overload Warning

+ (20 – 45 W)

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x
Rating

(1) x 12V x 4.5 Ah

(1) x 12V x 7.0 Ah

Approved Battery
Manufacturers:

CSB, Panasonic, BB Battery, and Yuasa

Transfer Time

2 – 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries:
> 4 minutes

Back-up Time:
Full load
Half load

12 minutes

Recharge Time

7-10 hours to 90% capacity, after full discharge into 100% resistive
load

ENVIRONMENTAL

Operating Temperature

+32° F to + 104° F (0° C to +40° C)

Storage Temperature

+5° F to + 122° F (-15° C to +50° C)

Relative Humidity

0% to 90%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating

Audible Noise

< 40 dBA, at 1 meter

AGENCY

Safety

UL 1778, c-UL Listed

Surge

IEEE C62.41 Category A

ESD

IEC 801-2, Level 3, Criterion< 2

Susceptibility

IEC 801-3, Level 3, Criterion< 2

Electrical Fast
Transient/Burst

IEC 801-4, Level 4, Criterion< 2

Emissions

FCC Part 15, Subpart B, Class B

Transportation

ISTA Project 1A

Advertising