TROUBLESHOOTING

If the UPS fails to operate properly, turn off the unit and repeat the steps in the
installation section of this manual. If the problem persists, refer to the chart
below:

PROBLEM

CAUSE

SOLUTION


UPS will not start


Overload/Short Circuit


Check fuse at rear of UPS. If blown, replace it
and restart the UPS. For further help, call your
Liebert representative


UPS starts on
battery, but will
not switch to AC


UPS not plugged in


Fuse blown

Power not available at
utility receptacle

Input voltage below
threshold

AC overvoltage


Plug in power cord securely


Replace fuse and restart UPS

Call a qualified electrician


Wait until voltage rises to appropriate level
Voltage must be higher than 90 VAC

AC voltage must be less than 132 VAC


UPS shuts down


Overload/Short Circuit






Low Battery



Sitenet 1 Shutdown


Check the fuse holder at rear of UPS. If fuse is
blown, replace it and restart the UPS. If problem
persists, disconnect some of the equipment from
your UPS - the total wattage of your equipment
may exceed the capacity of the UPS. For
further help, call your Liebert representative

Turn OFF equipment and recharge UPS battery
for at least 7 to 10 hours. If problem persists,
contact your Liebert representative

Consult the Sitenet 1 User Manual or contact
your LAN administrator