Lennox Hearth Ladera-BK User Manual

Page 10

Advertising
background image

Figure 9

Insulated Chase Construction

Floor

Ceiling

Wall

• Must have the same firestopping

resistance as adjacent wall.

• Must have the same insulation as

adjacent ceiling.

• Follow local rules regarding framing

construction.

7’

(2.1 m)

Min.

Note: Floor and wall below the attic must be

insulated using the same insulation.

Attic Radiation

Shield

Roof Support

Storm Collar

Flashing

Drywall or Any Rigid

Material

2 x 4

FIREPLACE

1/2” Plywood

6’ 8”

(2 m)

Min.

Firestop

Insulate Joists

Same As Ceiling

Draft Stops

Firestop

CTDT

Termination

Note: Non-

Combustible

Chase

Flashing

Must Be

Used To

Cover

Chase

Opening

Optional

Insulation

In Outside

Walls Of

Chase

Solid

Continuous

Surface

Outside

Base

Insulation

(Thermal Barrier)

8'

Level

8’

(2.4 m)

Level

Facing

1. Combustible material must be installed flush

with the fireplace. It may not project in front

of and on the fireplace (i.e. the steel facade

of the fireplace) (Figure 10).

2. Non-combustible materials such as brick,

stone or ceramic tile may project in front of

and onto the fireplace facing up to the tiling

flange (Figure 13).

Mantel and Facing

The mantel must be installed at least 39’’ (990

mm) above the base of the fireplace (Figures

7b and 11).

1

5

3

4

1. Fireplace
2. Tiling flange
3. Wood frame (2” x 3” min)
4. Drywall
5. Tiles or brick

Fireplace Frame Section

(Top View)

Figure 10

Figure 11

Mantel

Rock Board

or Other

Noncombustible

Facing

39’’ (990 mm)

Drywall

2” X 3” Min.

(51mm x 76mm)

Spacer

Mantel and Facing (Side View)

2

Rock Board

or Other

Noncombustible

Facing

Drywall

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

10