SEQUENCE OF OPERATION

IMPINGER ADVANTAGE

SERIAL NUMBER N28654 AND ABOVE

(OVENS WITH PUSH BUTTON CONTROLS)

MODEL 1454

220/380VAC

50 HZ.

3 PHASE

MODEL 1455

240/415VAC

50 HZ.

3 PHASE

POWER SUPPLY

Electrical power is to be supplied to the oven by a five conductor

service.

Brown conductor is hot.

Black conductor is hot.

Black conductor is hot.

Blue conductor is neutral.

Green conductor is ground.

CONTROL BOX AUTO

COOL DOWN

When the temperature in the control box reaches 120

°F ± 3°F (48.9°C

± 1.7°C), the cooling fan thermostat will switch power to the control

box cooling fan. The thermostat will interrupt power to the cooling fan
when the control box temperature falls to 100

°F ± 3°F (37°C ± 1.7°C).

MAIN FAN CIRCUIT

Electrical power is permanently supplied through three 50 A fuses to

the normally open contacts of the heat relay. Power is also supplied,

through the 10 Amp motor and control fuse, through the normally

closed control box hi-limit thermostat, to the normally open oven power

switch. Power is also supplied to the control box cooling fan

thermostat. Closing the oven power switch supplies line voltage to the

main fan motor. Closing the oven power switch also supplies line

voltage to the heat circuit and to the primary of the oven control

transformer.

HEAT CIRCUIT

Closing the oven power switch supplies line voltage through the main

fan air pressure switch, through the normally closed oven cavity hi-limit

thermostat, to the oven control

TEMPERATURE CONTROL Closing the oven power switch supplies line voltage to the primary of

the control transformer and through the air pressure switch and oven

cavity hi-limit, to the oven control. Secondary voltage, 24VAC, is

supplied to the oven control. The oven control is set to desired

temperature. The thermocouple will provide varying millivolts to the

oven control. The oven control supplies line voltage to the heat

contactor at intermittent intervals to maintain desired temperature. The

display on the oven control will indicate when the heat contactor is

energized.

NOTE: The display also indicates oven temperature.

CONVEYOR DRIVE

Closing the oven power switch supplies line voltage to the conveyor

motor and to the primary of the control transformer. Secondary

voltage, 24VAC, is supplied to the oven control. Setting the oven

control to the desired time outputs voltage, through a reversing switch,

to the conveyor motor.

NOTE: The conveyor system uses a hall effect sensor and magnet to

prove operation of the conveyor motor. If the motor is not running,

“BELT JAM” is indicated on the display.

SCHEMATIC DIAGRAM