Default Thermostat Settings

Default Thermostat settings are in table 1.

Table 1

Default Thermostat Settings

Mode

Heat

Setpoint

70°F (or 21°C)

Fan

Auto

Filter Reminder

OFF (reminder setting = 0)

Equipment Protection
Timers

reset back to zero

Technical Specifications

Thermostat Type

Electronic nonprogrammable thermostat for 1H/1C, heat
pump with electric or gas backup heat source, non−power
robbing applications.

Power Supply Range

18VAC − 30VAC (24VAC nominal), 60Hz

Temperature Display

Display Scale: Fahrenheit or Celsius user selectable (via
DIP switches)
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
Display Accuracy: +/−1°F

Temperature Measurement Range

Measurement Scale: Fahrenheit
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average of
the last four measurements.

Temperature Setpoint Range

Setting range: 50°F (10°C) to 90°F (32°C)
Setting resolution: 1°F (1°C)

Fan Control

AUTO or ON modes.

Backup Heat Source Selection

Electric or gas furnace, selectable via DIP switch #5 (Aux or
Dual, respectively). See also Thermostat Output section.

I/O Relays

All thermostat relays are latching type to minimize power
consumption. See table 2.

Table 2

51M33 Terminal Designations

Connections

Description

O

Reversing valve, cool active

B

Reversing valve, heat active

R

24VAC

G

Fan control

Y1

First stage cooling/heating, compres-
sor generated

W1

Auxiliary heating, furnace generated

L

Service Indicator

C

24VAC common

E

Emergency heat

T

Outdoor temperature sensor
connection 1

T

Outdoor temperature sensor
connection 2

Equipment Protection Timers

Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes

Minimum backup furnace cycle time (elapsed time be-
tween any furnace activation and the next furnace activa-
tion): 6 minutes.

Minimum elapsed time between any compressor activation
and the next compressor activation: 6 minutes.

NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.

Equipment Protection Override

Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.

Over−Temperature Protection

Thermal mechanical switch opens W1 at 93°F+/−6°F.

Filter Reminder

Settings of 0 (Off), 1, 3, 6 or 12 months are available. When
programmed time has elapsed, a FILTER indicator is dis-
played.

Balance Point

0°F (OFF) to 55°F, user selectable.