Equipment Protection Override

Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.

Over−Temperature Protection

Thermal mechanical switch opens W1 at 93°F+/−6°F.

Filter Reminder

Settings of 0 (Off), 1, 3, 6 or 12 months are available. When
programmed time has elapsed, a FILTER indicator is dis-
played.

Service Reminder

The SERVICE indicator is displayed only under the follow-
ing conditions:

S

if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the R terminal;

OR

S

if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of programmed
temperature setpoint, heat/cool and fan mode settings, fil-
ter reminder status, and equipment protection timers). Af-
ter 24 hours of power loss, programmed settings will be lost
and replaced with default settings.

IMPORTANT

Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to be
retained for the specified time.

LCD Backlight

Activated for 8 seconds when any key is pressed.

NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is normal
and will no longer occur after the electrical disturbance has
passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH

Thermostat Output Table

The following table depicts the 51M32 thermostat output states for various input conditions. See table 2.

Table 2

Thermostat Outputs

Condition

W1

Y1

G

Gas Heat, Auto Fan

heat demand

X

cool demand

X

X

no demand

Gas Heat, Continuous Fan

heat demand

X

X

cool demand

X

X

no demand

X

Electric Heat, Auto Fan

heat demand

X

X

cool demand

X

X

no demand

Electric Heat, Continuous Fan

heat demand

X

X

cool demand

X

X

no demand

X

NOTE −
X = output is activated with 24VAC.