Thermostat Output States

Condition

W1

Y1

G

O

E

Electric Heat Backup − No Outdoor Sensor

small heat demand

X

X

large heat demand

X

X

X

emergency heat demand

X

X

cool demand

X

X

X

no demand

dc

Gas Heat Backup (Dual Fuel) − No Outdoor Sensor

small heat demand

X

X

large heat demand

X

emergency heat demand

X

cool demand

X

X

X

no demand

dc

Electric Heat Backup − Outdoor Sensor Attached

small heat demand (BBP)

X

X

large heat demand (BBP)

X

X

X

small heat demand (ABP)

X

X

large heat demand (ABP)

X

X

emergency heat demand

X

X

cool demand

X

X

X

no demand

dc

Gas Heat Backup (Dual Fuel) − Outdoor Sensor Attached

small heat demand (BBP)

X

large heat demand (BBP)

X

small heat demand (ABP)

X

X

large heat demand (ABP)

X

emergency heat demand

X

cool demand

X

X

X

no demand

dc

NOTE −

S

X = output is activated with 24VAC

S

dc: does not care (output can be in either state, i.e., either active or inactive)

S

BBP: outdoor temperature is below balance point

S

ABP: outdoor temperature is above balance point

S

small heat demand: temperature is between (setpoint − 1.5°F) and (setpoint − 0.5°F), and 30-minute upstage
timer has not expired (see Normal Heat Mode graph)

S

large heat demand: temperature is below (setpoint − 1.5°F), or 30-minute upstage timer has expired (see Nor-
mal Heat Mode graph)

S

the state of the B terminal is opposite the state of the O terminal.

S

data above are tabulated for AUTO fan setting. If fan setting is ON, the fan is activated in all cases.