Warning, Operation indications, Error indications – Linear LRA User Manual

Page 23: Power-up display, Idle condition, Last gate position/condition, Pre-start delay, Reverse delay, Run timer, Entrapment

Advertising
background image

LRA Linear Residential Actuator Installation Guide

- 21 -

228158 Revision X13 2-3-2009

Operation Indications

During normal operation, the Controller’s displays will
indicate current operating conditions and status .

Power-up Display

When the Controller powers up, dashes will show on the
display for one second, then the firmware version number
will be displayed for one second .
Exiting programming restarts the Controller . The power-up
display will show upon the restart .

Idle Condition

While the Controller is idling, waiting for a command, the
display will show circulating dashes .
For DC models only - Clockwise : Batteries discharging,

Counterclockwise : Batteries charging

Last Gate Position/Condition

When the gate moves or stops, the display will show the
status for up to one minute .

Stop is displayed as

•

St

Full Close is displayed as

•

FC

Full Open is displayed as

•

FO

Entrapment is displayed as

•

En

Pre-start Delay

During the pre-start delay, the display will countdown the
number of seconds remaining before the operator starts .

Reverse Delay

If the gate travel direction is reversed from a user activation or
reversing device, and a reverse delay is set, the display will count
down the delay time in seconds before the operator restarts .

Run Timer

While the gate is opening or closing, the number of seconds
running time is displayed .

Error Indications

During abnormal operation, the Controller’s displays and
beeper will indicate the error condition that has occurred .

Entrapment

If an entrapment condition occurs detected by two repeated
open or close obstruction triggers, the Controller will lock
the operator out . The beeper will sound constantly and the
gate will not operate . To reset the Controller press the

STOP

button or press the

RESET button on the control box .

COMM LINK Connection Failure

In dual gate installations, if there is a connection failure between
the two operators, the

COMM LINK indicator will blink once a

second . During this condition the gate will not operate, except
if triggered by the

FIRE DEPT input, which functions normally .

MGT Obstacle Transmitter Trouble

If any MGT transmitters are used with the operator, their
supervision feature will alert the Controller if there is any
trouble with the transmitter . MGT transmitters send hourly
status reports and will send low battery reports when the
transmitter has a low battery . The MGT transmitters also
have a tamper detection switch that will trigger when their
case is opened .
When the Controller detects a low transmitter battery, a
tamper signal, or missing transmitter status reports, the
gate will still operate normally, but the beeper will change
as follows:

The Pre-start Alarm will beep twice as fast.

•

The Run Alarm will beep twice as fast and continue for five minutes

•

after the gate stops.
The sounder will “chirp” every five seconds when the gate is idle.

•

Correct the trouble (close case, replace battery, or replace
transmitter) to clear the obstacle transmitter trouble
indications .

Maximum Run Time Exceeded

If the Maximum Run Time is exceeded, the Controller stops
the operator the same as if a double obstacle has occurred
in an entrapment condition . The entrapment alarm sounds
constantly, and is cleared by pressing the

STOP button or the

RESET button on the cover . After the STOP or RESET button
is pressed, because the Maximum Run Time has been
exceeded, the sounder will beep twice every five seconds .
The next operation of the gate will clear the indication .

CONTROLLER ERROR CAUSES AND INDICATIONS

ERROR CAUSE

ERROR INDICATION

HOW TO CLEAR

TWO SAFETY REVERSALS (ON
SINGLE GATE OR ON EITHER
DUAL GATE)

En 00

, CONTINUOUS ALARM

BEEPER, GATE DISABLED

PRESS STOP BUTTON

MAXIMUM RUN TIMER
EXCEEDED ON OPENING

En 01

, AND

MAX RUN LED,

CONTINUOUS ALARM BEEPER,
GATE DISABLED

PRESS STOP BUTTON,
CLEARS CONTINUOUS ALARM,
THEN DOUBLE BEEP EVERY
5 SECONDS UNTIL NEXT
OPERATION

MAXIMUM RUN TIMER
EXCEEDED ON CLOSING

En 02

, AND

MAX RUN LED,

CONTINUOUS ALARM BEEPER,
GATE DISABLED

PRESS STOP BUTTON,
CLEARS CONTINUOUS ALARM,
THEN DOUBLE BEEP EVERY
5 SECONDS UNTIL NEXT
OPERATION

COMM LINK FAILURE

En 03

, AND

COMM LINK LED,

CONTINUOUS ALARM BEEPER
FOR 1 MINUTE, GATE DISABLED
(EXCEPT FOR FIRE DEPT INPUT)

PRESS STOP BUTTON, CLEARS
CONTINUOUS ALARM

GATE FULL OPEN RESULTING
FROM FIRE DEPT INPUT

En 04

, GATE DISABLED

PRESS STOP BUTTON

FAIL SAFE OR FAIL SECURE
BECAUSE OF AC POWER LOSS

En 05

, GATE DISABLED

BATTERY VOLTAGE MUST RISE
ABOVE 24 VDC

OTHER CONTROLLER IN
ENTRAPMENT (DUAL GATE)

En 06

, GATE DISABLED

CLEAR ENTRAPMENT ON OTHER
CONTROLLER (PRESS STOP)

LOW AC VOLTAGE AT
CONTROLLER

En 07

, GATE DISABLED

LOW VOLTAGE AC POWER MUST
RISE ABOVE 20 VAC

INPUT TRIGGERED DURING
ENTRAPMENT LOCKOUT

En 08

, GATE DISABLED

PRESS STOP BUTTON

COMPATIBILITY PROBLEM

En 09

, GATE DISABLED

UPDATE FIRMWARE AND RESET
BOTH PAIRED CONTROLLERS

EEPROM PROBLEM

En 10

, GATE DISABLED

TRY RESET, CALL TECH. SUPPORT

DC MOTOR MISMATCH

En 11

, GATE DISABLED

REPROGRAM MOTOR TYPE OR
CHANGE DC MOTOR BOARD,
NEXT GATE MOVEMENT WILL
RETRY DC MOTOR CHECK

MOTOR FAILURE

En 12

, GATE DISABLED

REPLACE MOTOR

MGT SUPERVISORY CONDITION
(TAMPER, LOW BATTERY,
MISSING HOURLY STATUS)

FAST BEEPS DURING PRESTART,
FAST BEEP RUN ALARM, CHIRP
EVERY 5 SECONDS AT IDLE

CLEARS WHEN MGT CONDITION
CLEARS

WARNING

The Stop and/or Reset button must be located in the line-of-

sight of the gate. Activation of the reset control shall not

cause the operator to start.