Direct Vent Retrofi t Of Existing Chimney System

An existing Class-A (wood-burning) Metal Chimney or Masonry
Chimney can be converted to a direct vent system. Use one of the
following chimney conversion kits listed below. Have the existing
chimney system inspected by a professional prior to the conversion.
If using Simpson Dura-Vent brand liner kit, see “IMPORTANT” note
at the top of page 12. The chimney conversion should not be applied
to the portion of the vent system that is in the room of the appliance.
Use only Co-Axial direct vent pipe (4” inner pipe, 6 5/8” outer pipe
as listed on page 12) from the appliance to the retro-connector into
converted fl ue system. Adhere to all specifi cations outlined in this
manual regarding clearances to combustibles, vertical and horizontal
vent length minimums and maximums, etc. Read all instructions in
this manual and provided by vent manufacturer with kit carefully before
starting the installation. Failure to follow the instructions may create
a fi re or other safety hazard, and will void the warranty. The following
Vent System components may be safely used with this appliance.

Table 7

Figure 17

Model

Brand: SECURITY SECURE VENT / Description

SV4MCK

Masonry Chimney Conversion Kit –Vertical term. Cap, cap adapter,

masonry cover, black adapter (to flex), 2 gear clamps

SV4CCK1

Factory Built Chimney Conversion Kit – for 6” I.D., 1” insulation.

SV4CCK2

Factory Built Chimney Conversion Kit – for 7” I.D., 1” insulation; 8”
I.D., 1” insulation; 6” I.D., 2” insulation.

SV4CCK3

Factory Built Chimney Conversion Kit – for 10” I.D., 1”
insulation; 7” I.D., 2” insulation; 8” I.D., 2” insulation.

Model

Brand: SIMPSON DURA-VENT / Description

934

Masonry Chimney Conversion Kit

931

Factory Built Chimney Conversion Kit A – for 6” I.D.;

932

Factory Built Chimney Conversion Kit B – for 6”, 7” & 8” I.D.

933

Factory Built Chimney Conversion Kit C – for 7” & 8” I.D.

Chimney DV Liner Kits

8 feet

1 inch

minimum

Support

Brackets

Wall
Stud

Installing Support Brackets

Install support brackets per vent manufacturers instructions.

Figure 15

Select Venting System - Horizontal Or Vertical
The following sections describe vertical (roof) and horizontal
(exterior wall) vent applications. Refer to the section relating to
your installation. A list of approved venting components is shown
on page 11 & 12.

Vertical

Horizontal

Combustion

Air

Exhaust

Placement:
Horizontal Runs - Requires
a support bracket every 5
feet (152 cm).

Vertical Runs - Requires
support brackets every 8
feet (244 cm) above the
stove vent outlet..

Vertical Vent Installation

Support Bracket Placement Diagram

Horizontal Vent Installation

Support Bracket Placement Diagram

Figure 16

Vertical

Rise

Elbow

Horizontal / Inclined Run

(

¹⁄₄" Rise per Foot of Horizontal Run in the

Direction away from the Stove)

Termination
Shown

Firestop/Spacer

Vent Sections

Support Bracket Spacing
Every 5 ft (1.52 m)

See figure for

vertical vent

Support

Brackets

Building

Support

Framing

Ceiling

Exterior

Wall

section support.