NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

19

V

H

H1

*Wall Firestop/Spacer

(SV4.5HF)

*Wall Firestop/Spacer

(SV4.5HF)

*When using Secure Flex,

use Firestop/Spacer

SF4.5HF

**Ceiling

Firestop/Spacer

(SV4.5VF)

**Note - When using

Secure Flex, use

Firestop/Spacer SF4.5VF

H1

V

H

*Wall

Firestop/Spacer

(SV4.5HF)

**Ceiling

Firestop/Spacer

(SV4.5VF)

*When using

Secure Flex, use

Firestop/Spacer

SF4.5HF

**When using

Secure Flex, use

Firestop/Spacer

SF4.5VF

Example: If 20 feet of (H) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of
(V) vertical, you are allowed 5 feet of (H) horizontal run, up
to a maximum horizontal run of 20 feet.

See

Table 3 on page 18 as an aid in venting component

selection for a particular range of exterior wall thick-
nesses.

TABLE H

H

+H

1

Maximum

H Maximum

V Minimum

feet

feet

feet

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + H + H1 = 40 feet (12.2 m) Max.

H = 8 feet (2.438 meters) Max.

H + H1 = 20 feet (6.096 meters) Max.

(meters)

(meters)

(meters)

Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical
vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed 5
feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.

An elbow is acceptable as 1 foot of vertical rise
except where an elbow is the only vertical
component in the system. See Figure 34.

H

+ H

1

Maximum

V Minimum

feet

feet

3

(0.914)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V +

H

+ H

1

= 40 feet (12.2 m) Max.

H

+ H

1

= 20 ft. (6.096 m) Max.

TABLE J

(meters)

(meters)

HORIZONTAL VENT FIGURES/TABLES (continued)

Figure 36

- Rear Vent - TWO 90 DEGREE ELBOWS

Figure 37

- Top Vent - TWO 90 DEGREE ELBOWS

See

Table 3 on page 18 as an aid in venting component

selection for a particular range of exterior wall thicknesses.

Square termination (SV4.5HT-2) shown.

Square termination (SV4.5HT-2) shown.