NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

5

12

X

Roof Pitch is X/12

2 FT
MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum
Clearance to Combustibles

h

c

t

i

P

f

o

o

R

H

)

t

e

e

f

(

2

1

/

6

o

t

t

a

l

F

0

.

1

2

1

/

7

o

t

2

1

/

6

r

e

v

O

5

2

.

1

2

1

/

8

o

t

2

1

/

7

r

e

v

O

5

.

1

2

1

/

9

o

t

2

1

/

8

r

e

v

O

0

.

2

2

1

/

0

1

o

t

2

1

/

9

r

e

v

O

5

.

2

2

1

/

1

1

o

t

2

1

/

0

1

r

e

v

O

5

2

.

3

2

1

/

2

1

o

t

2

1

/

1

1

r

e

v

O

0

.

4

Figure 4

APPLIANCE AND VENT CLEARANCES

Vertical Vent Termination Clearances

VENT TERMINATION CLEARANCES

These instructions should be used as a guide-
line and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and -
B149.2 in Canada.

The appliance is approved with zero clearance
to combustible materials on all sides (as de-
tailed in

Table 2 ), with the following excep-

tion: When the unit is installed with one side
flush with a wall, the wall on the other side of
the unit must not extend beyond the front edge
of the unit. In addition, when the unit is re-
cessed, the side walls surrounding the unit
must not extend beyond the front edge of the
unit. See

Figure 2.

Terminate single vent caps relative to building
components according to

Figure 4. Terminate

multiple vent terminations according to the
installation codes listed on this page.

Horizontal Vent Termination Clearances

The horizontal vent termination must have a
minimum of 3" (76 mm) clearance to any
overhead combustible projection of 2-1/2" (64
mm) or less. See

Figure 5. For projections

exceeding 2-1/2" (64 mm), see

Figure 5. All

horizontal terminations may be located as
close as 6" (152mm) to any (non-combustible
and combustible) exterior sidewall. This dis-
tance may be decreased to 2" (51mm) for non-
combustible exterior sidewalls only, if the
SV4.5HT-2 termination is used. For additional
vent location restrictions refer to

Figure 8 on

page 7.