8.0 COMBUSTION AND VENTILATION AIR

This heater shall not be installed in a confined space or unusually tight

construction unless provisions are provided for adequate combustion and

ventilation air. The heater may be located in unusually tight construction

provided the space is unconfined, or if confined, is provided with two

permanent openings communicating directly with an additional room(s)

of sufficient volume so that the combined volume of all connected spaces

meets the criteria for an unconfined space, (National Fuel Gas Code

NFPA 54 / ANSI Z223.1 - latest edition, Section on Air for Combustion

and Ventilation. Generally 50 ft

3

per 1,000 BTU input of all operating

appliances in the space.

The National Fuel Gas Code, ANSI Z223.1/NFPA 54, defines a confined

space as a space whose volume is less than 50 ft

3

per 1,000 BTU/Hr

(4.8 m

3

per kW) of the aggregate input rating of all appliances installed

in that space and an unconfined space as a space whose volume is not

less than 50 ft

3

per 1,000 BTU/Hr (4.8 m

3

per kW) of the aggregate input

rating of all appliances installed in that space.

Rooms communicating directly with the space in which the appliances

are installed, through openings not furnished with doors, are considered

a part of the unconfined space.

Unusually tight construction is defined as construction where:

a. Wall and ceilings exposed to the outside atmosphere have a continu-

ous water vapor retarder with a rating of one perm (6 X 10-11 kg per

pa-sec-m

2

) or less with openings gasketed or sealed;

b. Weather stripping has been added on operable windows and doors;

and

c. Caulking or sealants are applied to areas such as joints around window

and door frames, between sole plates and floors, between wall ceiling

joints, between wall panels, at penetrations for plumbing, electrical,

and gas lines, and at other openings.

Use the following equations to determine if you have a confined or

unconfined space.

1. Determine the volume of space — ft

3

.

Length x Width x Height = _____ ft

3

(Include adjoining rooms with doorless passageways or ventilation

grills between rooms).

Example: 24' (L) x 16' (W) x 8' (H) = 3072 ft

3

. Divide the volume of space by 50 ft

3

to determine the maximum BTU/Hr

the space can support.

______ (volume of space – ft

3

)/ 50 ft

3

=

(Maximum BTU/Hr the space can support)

Example: 3072 ft

3

/ 50 ft

3

= 61.44

or 61,440 BTU/Hr the space can support.

3. Add the BTU/Hr of all the fuel burning appliances in the space.

Vent-Free heater

_______ BTU/Hr

Gas appliance #1*

_______ BTU/Hr

Gas appliance #2 +

_______ BTU/Hr

Gas appliance #3 +

_______ BTU/Hr

Total =

_______ BTU/Hr

Example:

Vent-free heater #1 9,000 BTU/Hr

Vent-free heater #2 23,000 BTU/Hr

Gas appliance #1 35,000 BTU/Hr

(water heater)

Total = 67,000 BTU/Hr

* Do not include direct-vent gas appliances. Direct-vent is sealed com-

bustion and draws combustion air from the outdoors.

4. Compare the maximum BTU/Hr the space can support with the actual

amount of BTU/Hr used.

_______ BTU/Hr (max. the space can support)

_______ BTU/Hr (actual amount of BTU/Hr used)
Example:

61,440

BTU/Hr (max. the space can support)

67,000 BTU/Hr (actual amount of BTU/Hr used)

The space in the previous example is a confined space because the

actual BTU/Hr used is more than the maximum BTU/Hr the space can

support. You must provide additional fresh air.

Your options are:

a. Rework equations adding the space of adjoining room(s). If the extra

volume provides an unconfined space, then remove door or add

ventilation grills between rooms. Refer to National Fuel Gas Code,

ANSI Z223.1/NFPA 54-latest edition, Section "Air for Combustion and

Ventilation".

b. Vent room directly to the outdoors. Refer to National Fuel Gas Code,

ANSI Z223.1/NFPA 54-latest edition, Section "Air for Combustion and

Ventilation".

c. Install a lower BTU/Hr heater to make the area an unconfined space.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space

can support, then the space is an unconfined space. You will need no

additional fresh air ventilation for an unconfined space.

WARNING

If the area in which the heater may be operated is

smaller than that defined as an unconfined space

or if the building is of unusually tight construc-

tion, provide adequate combustion and ventilation

air by one of the methods described in the national

fuel gas code, ANSI Z3.1/NFPA 54, Air for Combus-

tion and Ventilation Or applicable local codes.