MAINTENANCE

The PowerSure ProActive UPS requires very little maintenance. The batteries
are valve regulated, nonspillable, lead acid, and require that they be kept
charged to obtain their designed life. When ON, the UPS continuously charges
the batteries when connected to the utility supply.

When storing the UPS for any length of time, it is recommended to plug in and
turn on the UPS for at least 24 hours every four to six months to ensure full
recharge of the batteries.

The following will help ensure trouble-free operation for years to come:
- Vacuum dust from the ventilation intake occasionally.
- Wipe the cover periodically with a dry cloth.

-

Occasionally press the UPS test button to test the condition of the batteries.

FUSE REPLACEMENT PROCEDURES

Insert flat blade screw
driver into slot and pull
fuse holder out to remove

AC Inlet

Fuse Holder

Input Fuse

Spare Fuse

CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the
input cord from the AC input power supply and from the UPS.

1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and

pulling out as indicated in the figure above.

2. Remove the input fuse.
3. Remove the spare fuse from its position by using the screwdriver to push it

out.

4. Place spare fuse in the input fuse position, and replace the fuse holder. The

fuse holder will lock into position.

5. Reconnect the input power lead to the UPS, and the input power lead to the

input AC supply.

6. Restart the UPS. The UPS is ready for normal operation.

ProActive Model #

Fuse Type

PSA350-120

5A / 125V

PSA470-120

6A / 125V

PSA700-120

8A / 125V

PSA350-230

3.15A / 250V

PSA470-230

4A / 250V

PSA700-230

6.3A / 250V