230V SPECIFICATIONS

Model Number

PSA350-230

PSA470-230

PSA700-230

Model Rating VA/W

350VA/210W

470VA/282W

700VA/420W

DIMENSIONS: mm (in)

Unit
H x W x D

166 x 115.5 x 352.5

(6.5 x 4.5 x 13.9)

166 x 115.5 x 352.5

(6.5 x 4.5 x 13.9)

166 x 115.5 x 352.5

(6.54 x 4.55 x 13.9)

Shipping
H x W x D

226 x 156 x 404

(8.8 x 6.2 x 15.8)

226 x 156 x 404

(8.8 x 6.2 x 15.8)

226 x 156 x 404

(8.8 x 6.2 x 15.8)

WEIGHT: kg (lbs)

Unit

6 (13.2)

7 (15.4)

10 (22)

Shipping

6.8 (15)

7.8 (17.2)

10.8 (23.8)

INPUT AC PARAMETERS

Voltage Range without
Battery Operation

166 to 275VAC

Line to Boost Transfer

198VAC

Line to Buck Transfer

250VAC

Frequency

47-53 Hz or 57-63 Hz; auto sensing

Input Power Receptacle

EN60320/C14 recessed plug

OUTPUT AC PARAMETERS

Output Receptacles

(4) EN60320/C13 sockets, (2) detachable EN60320-2-2 1.8m (6’) power
cords

Voltage (Battery Mode)

230 VAC + 5%

Waveform (Battery Mode)

Stepped Sinewave

Voltage (Normal)

V

IN

* (1.0)

Voltage (Boost Mode)

V

IN

* (1.13)

Voltage (Buck Mode)

V

IN

* (0.85)

Frequency

50 Hz or 60 Hz; auto sensing

Overload Warning
(Utility and Battery Modes)

101 – 120%

Overload Shutdown
(Utility and Battery Modes)

Overload

+ (15 – 30W)

Overload

+ (20 – 40W)

Overload

+ (30 – 60W)

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x Rating

(1) x 12V x 7.0 Ah

(1) x 12V x 7.0 Ah

(1) x 12V x 10 Ah

Approved Battery
Manufacturers:

CSB, Panasonic, and Yuasa

Transfer Time

4 – 6 ms typical
At 25°C (77°F), resistive loading, with fully charged batteries:
> 5 minutes typical

Back-up Time:
Full load
Half load

> 15 minutes typical

> 12 minutes typical

> 13 minutes typical

Recharge Time

7-10 hours to 90% capacity, after full discharge into 100% resistive load

ENVIRONMENTAL

Operating Temperature

0° C to +40° C (+32° F to + 104° F)

Storage Temperature

-15° C to +50° C (+5° F to + 122° F)

Relative Humidity

0% to 90%, non-condensing

Operating Elevation

Up to 3000 m. (10,000 ft) at 35° C (95° F) without derating

Audible Noise

<40 dBA, at 1 meter

AGENCY

Safety

EN50091-1, TUV/GS listed, CE Compliance Mark

Surge

IEC 801-5, Level 3

ESD

IEC 801-2, Level 3, Criterion< 2

Susceptibility

IEC 801-3, Level 3, Criterion< 2

Electrical Fast
Transient/Burst

IEC 801-4, Level 4, Criterion< 2

Emissions

EN50091-2, EN55011 Class B

Transportation

ISTA Project 1A

Advertising