115v specifications – Liebert 115V User Manual

Page 8

Advertising
background image

8

115V SPECIFICATIONS

Model Number

PSA350-120

PSA470-120

PSA700-120

Model Rating VA/W

350VA/210W

470VA/282W

700VA/420W

DIMENSIONS: in (mm)

Unit
H x W x D

6.5 x 4.5 x 13.9

(166 x 115.5 x 352.5)

6.5 x 4.5 x 13.9

(166 x 115.5 x 352.5)

6.5 x 4.5 x 13.9

(166 x 115.5 x 352.5)

Shipping
H x W x D

8.8 x 6.2 x 15.8

(226 x 156 x 404)

8.8 x 6.2 x 15.8

(226 x 156 x 404)

8.8 x 6.2 x 15.8

(226 x 156 x 404)

WEIGHT: lbs (kg)

Unit

13.2 (6)

15.4 (7)

22 (10)

Shipping

15 (6.8)

17.2 (7.8)

23.8 (10.8)

INPUT AC PARAMETERS

Voltage Range
without Battery Operation

87 to 144VAC

Line to Boost Transfer

104VAC

Line to Buck Transfer

124VAC

Frequency

47-53 Hz or 57-63 Hz; auto sensing

Input Power Cord

6 ft. detachable, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

Output Receptacles

(4) 5-15R

Voltage (Battery Mode)

115 VAC + 5%

Waveform (Battery Mode)

Stepped Sinewave

Voltage (Normal)

V

IN

* (1.0)

Voltage (Boost Mode)

V

IN

* (1.16)

Voltage (Buck Mode)

V

IN

* (0.84)

Frequency

50 Hz or 60 Hz; auto sensing

Overload Warning
(Utility and Battery Modes)

101 – 120%

Overload Shutdown
(Utility and Battery Modes)

Overload

+ (15 – 30W)

Overload

+ (20 – 40W)

Overload

+ (30 – 60W)

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x Rating

(1) x 12V x 7.0 Ah

(1) x 12V x 7.0 Ah

(1) x 12V x 10 Ah

Approved Battery
Manufacturers:

CSB, Panasonic, and Yuasa

Transfer Time

4 – 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries:
> 5 minutes typical

Back-up Time:
Full load
Half load

> 15 minutes typical

> 12 minutes typical

> 13 minutes typical

Recharge Time

7-10 hours to 90% capacity, after full discharge into 100% resistive load

ENVIRONMENTAL

Operating Temperature

+32° F to + 104° F (0° C to +40° C)

Storage Temperature

+5° F to + 122° F (-15° C to +50° C)

Relative Humidity

0% to 90%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating

Audible Noise

< 40 dBA, at 1 meter

AGENCY

Safety

UL 1778, c-UL Listed

Surge

IEEE C62.41 Category A

ESD

IEC 801-2, Level 3, Criterion< 2

Susceptibility

IEC 801-3, Level 3, Criterion< 2

Electrical Fast Transient/Burst

IEC 801-4, Level 4, Criterion< 2

Emissions

FCC Part 15, Subpart B, Class B

Transportation

ISTA Project 1A