Operation – Lincoln VANTAGE 500 User Manual
Page 26
B-9
OPERATION
B-9
Vantage 500 CUMMINS
TABLE B.5 Vantage Extension Cord Length Recommendations
Current
(Amps)
15
15
20
20
25
30
38
50
Voltage
(Volts)
120
240
120
240
240
240
240
240
Load
(Watts)
1800
3600
2400
4800
6000
7200
9000
12000
30
60
(9)
(18)
40
75
30
60
(12)
(23)
(9)
(18)
75
150
50
100
90
75
(23)
(46)
(15)
(30)
(27)
(23)
125
225
88
175
150
120
100
(38)
(69)
(27)
(53)
(46)
(37)
(30)
175
350
138
275
225
175
150
125
(53)
(107)
(42)
(84)
(69)
(53)
(46)
(38)
300
600
225
450
250
300
250
200
(91)
(183)
(69)
(137)
(76)
(91)
(76)
(61)
Maximum Allowable Cord Length in ft. (m) for Conductor Size
Conductor size is based on maximum 2.0% voltage drop.
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
4 AWG
TABLE B.4 Vantage Simultaneous Welding and Power Loads
Welding Output
Permissible Power Watts
Permissible Auxiliary
at NEMA Voltage
(Unity Power Factor)
Current in Amperes
(V=.04I + 20)
@ 120VAC * +/- 10% @ 240 VAC +/- 10%
0-250A/30V
12,000
100**
50
350A/34V
8,100
68**
34
400A/36V
5,600
46
23
450A/38V
2,900
24
12
500A/40V
0
0
0
* Each duplex receptacle is limited to 20 amps.
** Not to exceed 50A per 120 VAC branch circuit when splitting the 240 VAC output.