SPECIFICATIONS

Model # / Stock #

PS250-50/PS250-50S

PS400-50 / PS400-50S

PS600-50 / PS600-50S

Model Rating

250 VA / 150 W

400 VA / 240 W

600 VA / 360 W

Dimensions: mm
Unit (W x D x H)

90 x 262 x 175

109 x 262 x 186

124 x 262 x 216

Shipping (W x D x H)

181 x 365 x 303

212 x 482 x 292

237 x 482 x 334

Weight: Kg
Unit

4

5.7

9

Shipping

4.6

7

10.5

AC Parameters
Receptacles

(2) CEE-22

(4) CEE-22

(4) CEE-22

Input Voltage Range

180-300 VAC, Single Phase, 2 Wire Plus Earth

Low Voltage Transfer Point

190 VAC, User Selectable to 180 or 200 VAC

High Voltage Transfer Point

270 VAC

270 VAC, User Selectable to 280 VAC

Input Frequency Range

47 – 53 Hz, 57 – 63 Hz

Spike Protection

80 Joules

Output Voltage (on battery)

230 VAC, ± 5%

Output waveform (on battery)

Stepped Sine Wave

Max. Output Current at 230 V

1.1 A

1.7A

2.6A

Output Frequency

50 or 60 Hz, ± 5%

Max. Overload Capacity

115% of Power Rating

Battery
Type

Valve-Regulated Lead Acid

Qty x Voltage x Rating

1 x 12 V x 4.5 AH

1 x 12 V x 7 AH

2 x 12 V x 7 AH

Back-up Time

6 minutes at full load

Time from Low Battery Alarm
to Shutdown

Approximately 2 Minutes, depending on load

Recharge Time

8 – 10 Hours to 90% Capacity

Battery Life

3 – 5 Years Typical

Transfer Time to/from Inverter

2 – 6 msec. Typical

Agency Approvals
Safety

EN 50091-1

RFI

Meets EN 55022 Class B, IEC 801-2, 3, 4

Surge Protection

Meets IEC 801-5 (Draft)

MTBF (Bellcore Method)

100,000 Hours (Excluding Battery)

Environmental Standards
Operating Temperatures

+10° C to +40° C

Storage Temperatures

-20° C to +40° C (High Temperatures Reduce Battery Life)

Cooling

Convection

Audible Noise

Less than 40 dB @ 1 meter

Operating Elevation

Up to 3,000 m

Storage Elevation

Up to 10,000 m