250 VA LED & ALARM INDICATIONS

Condition

Green AC

Light (4)

Audible Alarm

Status

NORMAL/START UP

On after Beep

Single Beep, then Off

Operate

Start-Up Test Fail

On after Beep

Fast Beep for 15 Sec and then Off

Operate

Input Frequency Mismatch with
Option Switch Setting

Input Voltage Below Threshold

Off

Continuous

Will Not Start

Overload/Short Circuit

Off

Continuous for 15 Sec and then Off

Will Not Start

NORMAL MODE

On

Off

Operate

Battery Test Fail

On

Fast Beep for 15 Sec and then Off

Operate

Overload/Short Circuit

Off

Continuous for 15 Sec and then Off

Shutdown

BACKUP MODE

Off

Slow Beep

Operate

Low Battery Alarm

Off

Fast Beep

Warn of Shutdown

Low Battery Shutdown

Off

Continuous for 15 Sec and then Off

Shutdown

Main Overvoltage
(transfer enabled)

Off

Slow Beep

Operate

The UPS starts and repeats the battery test sequence every hour until the test is passed.

400/600 VA LED & ALARM INDICATIONS

Condition

Green AC

Light (4)

Amber

Battery

Light (2)

Red Warning

Light (3)

Audible Alarm

Status

NORMAL/START UP

On

Flash Once &

then Off

Off

Single Beep and then

Off

Operate

Start-Up Test Fail

Off

Off

On

Continuous for 15 Sec

and then Off

Will Not Start

Input Frequency Mismatch
with Option Switch Setting

Overload/Short Circuit

Off

On for 15 Sec

and then Off

Flash

Continuous for 15 Sec

and then Off

Will Not Start

Input Voltage Below
Threshold

Off

Off

Flash

Continuous for 15 Sec

and then Off

Will Not Start

NORMAL MODE

On

Off

Off

Off

Operate

Battery Test Fail

On

Off

On

N/A

Operate

Overpower

On

Off

Flash

Fast Beep

Alarm Only

Overload/Short Circuit

Off

On for 15 Sec

& then Off

Flash for 15

Sec & then Off

Continuous for 15 Sec

& then Off

Shutdown

Charger Fail

On

Off

On

Slow Beep

Alarm Only

BACKUP MODE

Off

On

Off

Slow Beep

Operate

Low Battery Alarm

Off

On

On

Fast Beep

Operate

Low Battery Shutdown

Off

On*

On*

Continuous for 15 Sec

& then Off

Shutdown

Mains Undervoltage

Off

On

Off

Slow Beep

Operate

Mains Overvoltage

Off

On

Flash

Slow Beep

Operate

Overload/Short Circuit
SiteNet 1 Shutdown

Off

On*

Flash*

Continuous for 15 Sec

& then Off

Shutdown

*If there is insufficient utility voltage, this indicator illuminates for 15 seconds then turns off to preserve the battery.