PROBLEM

CAUSE

SOLUTION

UPS will not start


Input voltage below
threshold

Overload/Short Circuit





Input frequency mis-
match with option switch
setting

Mains overvoltage


Wait until mains voltage rises to appropriate level.


Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart
the UPS (See "Resetting Circuit Breaker'). If problem persists, disconnect
some of the equipment from UPS - the total wattage or all your equipment
may exceed the capacity of the UPS. If it still will not start, check your
computer equipment for short circuits. For further help, call your dealer.

Check Option Switch #1 on rear of UPS (6). Slide switch to left for OFF, to
right for ON. OFF = 60 Hz, ON = 50 Hz. The UPS frequency must match
the frequency of your input mains supply.

Mains voltage must be less than 270 VAC.

UPS starts on

battery, but will not

switch to mains

power.

(400 & 600 VA

only)


UPS not plugged in

Circuit breaker activated

Power not available at
utility receptacle


Plug in power cord securely.

Reset circuit breaker (see “Resetting Circuit Breaker”) and restart UPS.

Call a qualified electrician.


UPS shuts down.


Overload/Short Circuit





Low Battery


Sitenet 1 Shutdown
(400 & 600 VA only)


Check circuit breaker at rear of UPS (9). If it is activated, reset it and restart
the UPS (See "Resetting Circuit Breaker"). If problem persists, disconnect
some of the equipment from UPS - the total wattage of all your equipment
may exceed the capacity of the UPS. If it still will not start, check your
computer equipment for short circuits. For further help, call your dealer.

Turn OFF equipment and recharge UPS battery for at least 8 hours. If
problem persists, replace battery.

Consult the SiteNet 1 User Manual or contact your LAN administrator.