Thermostat Output Table

Table 5 depicts the 51M37 thermostat output states for var-
ious input conditions. The following notes described terms
used in the table.

NOTES:

S X = output is activated with 24VAC.
S BBP: outdoor temperature is below balance point
S ABP: outdoor temperature is above balance point
S In all cases, the state of the B terminal is opposite that

of the O terminal

S Data are tabulated for AUTO fan setting. If the fan set-

ting is ON, the G output is activated in all cases

S Upstage timers:

30 minutes (when upstaging from small to large
demand)

15 minutes (HEAT MODE ONLY − when upstaging
from large to very large demand)

S The temperature ranges expressed in the following

definitions of SMALL/LARGE/VERY LARGE" de-
mands are for guidance only; actual temperatures
may vary:

With a small HEAT demand, temperature is:
below setpoint –0.5F but above setpoint –1.5F
AND 30-minute upstage timer HAS NOT expired.

With a large HEAT demand, temperature is:
less than setpoint –1.5F
OR 30-minute upstage timer HAS expired.

With a very large heat demand, temperature is:
below setpoint –2.5F
OR 15−minute 2

nd

upstage timer HAS expired.

Emergency heat demand (only if emergency heat is
enabled): temperature is below setpoint –0.5F.

With a small COOL demand, temperature is:
above setpoint +0.5F but below setpoint +1.5F
AND 30-minute upstage timer HAS NOT expired.

With a large COOL demand, temperature is:
above setpoint +1.5F
OR 30-minute upstage timer HAS expired.

Table 5

THERMOSTAT OUTPUTS

Demand Condition

W1

E

Y1

Y2

G

O

Cooling Demands

SMALL

X

X

X

LARGE

X

X

X

X

No Demand

X

Heating Demands

w/Electric Backup

(no outdoor sensor)

SMALL

X

X

LARGE

X

X

X

Very LARGE

X

X

X

X

Emergency

X

X

No Demand

w/Gas Backup

(dual fuel; no outdoor sensor)

SMALL

X

X

LARGE

X

X

X

Very LARGE

X

Emergency

X

No Demand

w/Electric Backup

(outdoor sensor attached)

SMALL (Above Balance Point)

X

X

LARGE (ABP)

X

X

X

Very LARGE (ABP)

X

X

X

SMALL (Below Balance Point)

X

X

LARGE (BBP)

X

X

X

Very LARGE (BBP)

X

X

X

X

Emergency

X

X

No Demand

w/Gas Backup

(dual fuel; outdoor sensor attached)

SMALL (ABP)

X

X

LARGE (ABP)

X

X

X

Very LARGE (ABP)

X

SMALL (BBP)

X

LARGE (BBP)

X

Very LARGE (BBP)

X

Emergency

X

No Demand