Removing and Installing Thermostat

The thermostat hinges on tabs on the top of the subbase;
no tool is needed to remove the thermostat from the sub-
base. Pivot the bottom of the thermostat outward (releas-
ing the snaps), then lift up to remove.

To install it, first position the top tilted toward the wall brack-
et and align it until you feel the tabs and slots engage; then,
while the top is in place, pivot the bottom toward the wall
until the thermostat snaps into place.

Default Thermostat Settings

Default thermostat settings are in table 2 and the default
program is shown in table 3.

Table 2

Default Thermostat Settings

Mode

Heat (Perm. Hold)

Heat Setpoint (Perm Hold)

70°F (or 21°C)

Cool Setpoint (Perm Hold)

78°F (or 26°C)

Fan

Auto

Filter Reminder

OFF

Maintenance Reminder

OFF

Equipment Protection Timers

Reset Back to Zero

Autochangeover

OFF

Table 3

Default Program Settings (Time & Temp.)

Programs

Time

Temp.− Heat

Temp.− Cool

All days − A

6:00am

70

_F / 21°C

78

_F / 26°C

All days − B

8:00am

62

_F / 17°C

85

_F / 29°C

All days − C

6:00pm

70

_F / 21°C

78

_F / 26°C

All days − D

10:00pm 62

_F / 17°C

82

_F / 28°C

Thermostat Output Table

Table 4 depicts the 51M39 thermostat output states for var-
ious input conditions. The following notes described terms
used in the table.

Table 4

Thermostat Outputs

Condition

W1

W2

Y1

Y2

G

Gas Heat, Auto Fan

Heat Demand, SMALL

X

Heat Demand, LARGE

X

X

Cool Demand, SMALL

X

X

Cool Demand, LARGE

X

X

X

No Demand

Gas Heat, Continuous Fan

Heat Demand, SMALL

X

X

Heat Demand, LARGE

X

X

X

Cool Demand, SMALL

X

X

Cool Demand, LARGE

X

X

X

No Demand

X

Electric Heat, Auto Fan

Heat Demand, SMALL

X

X

Heat Demand, LARGE

X

X

X

Cool Demand, SMALL

X

X

Cool Demand, LARGE

X

X

X

No Demand

Electric Heat, Continuous Fan

Heat Demand, SMALL

X

X

Heat Demand, LARGE

X

X

X

Cool Demand, SMALL

X

X

Cool Demand, LARGE

X

X

X

No Demand

X

NOTE − X = output is activated with 24VAC.

NOTE − The temperature ranges expressed in the follow-
ing definitions of SMALL/LARGE" demands are for guid-
ance only; actual temperatures may vary.

With a SMALL heat demand, temperature is:
below setpoint –0.5F but above setpoint –1.5F
AND 30-minute upstage timer HAS NOT expired.

With a LARGE heat demand, temperature is:
less than setpoint –1.5F
OR 30-minute upstage timer HAS expired.

With a SMALL cool demand, temperature is:
above setpoint +0.5F but below setpoint +1.5F
AND 30-minute upstage timer HAS NOT expired.
With a LARGE cool demand, temperature is:
above setpoint +1.5F
OR 30-minute upstage timer HAS expired.