Page 9

51M39 SERIES 5/2

NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.

Equipment Protection Override

Both the minimum compressor OFF timer and the mini-
mum equipment cycle timer can be over−ridden by press-
ing and holding either the HEAT or COOL button down for 4
seconds.

Over−Temperature Protection

Thermal-mechanical switch opens W1 and W2 at
93°F+/−6°F.

Filter Reminder

Settings of Off, 1, 3, 6 or 12 (months of fan run time) are
available. When programmed time has elapsed, a FILTER
indicator is displayed.

Maintenance Reminder

Settings of Off, 6 or 12 (months of chronological time) are
available. When programmed time has elapsed, a mainte-
nance indicator MAINTENANCE" is displayed.

Service Reminder

The SERVICE indicator is displayed only under the follow-
ing conditions:

S

if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the R terminal;

OR

S

if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of clock setting,
program information, HOLD status, programmed temper-
ature setpoint, heat/cool and fan mode settings, filter re-
minder status, maintenance reminder status, and equip-
ment protection timers). After 24 hours of power loss,
programmed settings will be lost and replaced with default
settings.

IMPORTANT

Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to
be retained for the specified time.

LCD Backlight

Activated for 30 seconds when any button is pressed.

NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is nor-
mal and will no longer occur after the electrical disturbance
has passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH