Figure 10 rack mounting rails and slide assemblies, Caution – Liebert PowerSure PSI 1000 - 3000VA 60 Hz 120V User Manual

Page 17

Advertising
background image

Installation

11

4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the

inside of the rack mounting rails.

5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front

of the fixed rail assembly (see Figure 10).

6. Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail.
7. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes on the rear of the fixed

rail assembly.

8. Check alignment of fixed rails and tighten all screws to ensure locking action.

Figure 10 Rack mounting rails and slide assemblies

9. Lay the UPS in rack-mounting position on the fixed rails. The UPS should move smoothly forward

and backward on the fixed rails. If not, recheck alignment.

10. Use the extra M5 screws provided, secure front of the UPS to rack mounting rails to prevent the

UPS from sliding out of position.

11. Plug the PowerSure PSI’s attached 10 ft. (3m)

power cord into a dedicated wall receptacle

properly protected by a circuit breaker or fuse in

accordance with national and local electrical codes.

Use a 15A-rated device for the 1000 or 1440 VA

units, 20 amp for the 1920VA, 30 amp for the

2200VA or 3000 VA units. The wall receptacle

must be grounded.

12. Turn On the UPS by pressing the ON button.

Check that the AC Input Indicator is not flashing.

If it is flashing, refer to 11.0 - Troubleshooting.

Then turn On the connected equipment. The UPS

is now providing conditioned power to your

equipment.

!

CAUTION

Lifting equipment into rack may be a two-person job, depending on weight of equipment.

!

CAUTION

To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should

be segregated and run separately from power cables.

A - Washer

B - M5x12 Flat Screw

B

A

B

B

B

A

A

A

Vertical

overlay

for tower

UPS

Horizontal

overlay for

rack UPS

Advertising