0 specifications, Table 3 ups specifications, Pecifications – Liebert PowerSure PSI 1000 - 3000VA 60 Hz 120V User Manual

Page 32: Table 3, Ups specifications, 0 - specifications ). external battery

Advertising
background image

Specifications

26

12.0 S

PECIFICATIONS

Table 3

UPS specifications

Model Number

PS1000RT2-120

PS1440RT2-120

PS1920RT2-120

PS2200RT2-120

PS3000RT2-120

Power Rating, VA/W

1000VA/750W

1440VA/1080W

1920VA/1500W

2200VA/1650W

3000VA/2250W

Dimensions, W x D x H, in (mm)

Unit

3.43 x 22 x 17

(87 x 557 x 430)

3.43 x 22 x 17

(87 x 557 x 430)

3.43 x 24.1 x 17

(87 x 612 x 430)

3.43 x 24.1 x 17

(87 x 612 x 430)

3.43 x 24.1 x 17

(87 x 612 x 430)

Shipping 11.8 x 27.8 x 23.5

(300 x 706 x 598)

11.8 x 27.8 x 23.5

(300 x 706 x 598)

13.1 x 34 x 23.5

(333 x 864 x 598)

13.1 x 34 x 23.5

(333 x 864 x 598)

13.1 x 34 x 23.5

(333 x 864 x 598)

Weight, lbs (kg)

Unit

61.7 (28)

68.2 (31.0)

77.0 (35.0)

77.0 (35.0)

81.6 (37.0)

Shipping

80.7 (36.6)

85.8 (39.0)

95.9 (43.6)

95.9 (43.6)

100.5 (45.6)

Input AC Parameters

Surge Protection

570J

Voltage Range Without

Battery Operation

78VAC - 150VAC, configurable

Frequency Range

45 - 65 Hz (±0.1 Hz)

Input Power Cord

(attached)

10 ft. (3m),

NEMA 5-15 P

10 ft. (3m),

NEMA 5-15 P

10 ft. (3m),

NEMA 5-20 P

10 ft. (3m),

NEMA L5-30 P

10 ft. (3m),

NEMA L5-30 P

Output AC Parameters

Output Receptacles

(8)NEMA 5-15R

(8)NEMA 5-15R

(6) NEMA 5-15 R

(2) NEMA 5-20 R

T-Slot, accepts 15APlug

(6) NEMA 5-15 R

(2) NEMA 5-20 R

T-Slot, accepts 15APlug

(4) NEMA 5-15 R

(2) NEMA 5-20 R

T-Slot,accepts

15A Plug

(1) NEMA L5-30 R

Voltage (Normal mode)

110 / 120 / 127 VAC (configurable) ±10%

Voltage (Battery Mode)

110 / 120 / 127 VAC (configurable);

±5% before low battery warning; ±8% after low battery warning

Transfer Time

4-6 ms typical

Waveform

Sinewave

Frequency (Normal Mode)

45 - 65 Hz (±0.1 Hz)

Frequency (Battery Mode)

50 or 60 Hz (±0.5 Hz); auto sensing

Overload Warning

>100 - 110%

Overload Shutdown

>200% - short circuit; after 15 cycles (normal mode)

Battery Parameters

Type

Valve-regulated, nonspillable, lead acid

QuantityxVoltagexRating

4 x 12V x 7Ah

4 x 12V x 7Ah

6 x 12V x 7Ah

6 x 12V x 7Ah

6 x 12V x 9Ah

Backup Time

See Table 5 - Battery run times

Full Load

11

5

6

5

6

Half Load

26

16

19

16

16

Recharge Time

4 hours to 90% of rated capacity, after full discharge into resistive load

Environmental

Operating Temperature

+32°F to + 104°F (0°C to + 40°C)

Storage Temperature

+5°F to + 104°F (-15°C to + 40°C)

Relative Humidity

0% to 95%, non-condensing

Operating Altitude

Up to 10,000 ft. (3000m) at 95°F (35°C) without derating

Audible Noise

<40 dBA, internal fan(s) Off

<50 dBA, internal fan(s) On

<40 dBA, internal fan(s) Off

<60 dBA, internal fan(s) On

Advertising