6-5 REFRIGERATING CYCLE

- 14 -

Troubleshooting Chart

Leakage Detection

YES

YES

Check if compressor
runs.

Check if frost
forms in
Evaporator.

Observe the discharged
amount of Refrigerant.

Inject refrigerant in compressor
and check cooling operation.

Clogged by dust.

Gas leakage.

Faulty
Compressor.

Moisture Clog

Check if oil
leaks.

Frost formed normally

Normal amount

None or too much

(Find the leak and repair it)

Frost formed normally

No frost
or frost forms
in inlet only

Check Compressor

PARTIAL

Freezer

Low flowing sound of

A little higher

• Refrigerant level is low due

LEAKAGE

compartment and

Refrigerant is heard and

than ambient

to a leak.

Refrigerator don't

frost forms in inlet only.

temperature.

• Normal cooling is possible by

cool normally.

restoring the normal amount of

refrigerant and repairing the leak.

COMPLETE

Freezer

Flowing sound of refrigerant

Equal to ambient

• No discharging of Refrigerant.

LEAKAGE

compartment and

is not heard and frost isn't

temperature.

• Normal cooling is possible by

Refrigerator don't

formed.

restoring the normal amount of

cool normally.

refrigerant and repairing the leak.

PARTIAL

Freezer

Flowing sound of refrigerant

A little higher

• Normal discharging of the

RESTRICTION

compartment and

is heard and frost forms

than ambient

refrigerant.

Refrigerator don't

in inlet only.

temperature.

• The capillary tube is faulty.

cool normally.

WHOLE

Freezer

Flowing sound of refrigerant

Equal to ambient

• Normal discharging of the

RESTRICTION

compartment and

is not heard and frost isn't

temperature.

Refrigerant.

Refrigerator don't cool. formed.

MOISTURE

Cooling operation

Flowing sound of refrigerant

Lower than

• Cooling operation restarts

RESTRICTION

stops periodically.

is not heard and frost melts.

ambient

when heating the inlet of the

temperature.

capillary tube.

COMP-

Freezer and

Low flowing sound of

A little higher

• Low pressure at high side

RESSION

Refrigerator

refrigerant is heard and

ambient

of compressor due to low

don't cool.

frost forms in inlet only.

temperature.

refrigerant level.

NO COMP-

No compressing

Flowing sound of refrigerant

Equal to ambient

• No pressure in the high

RESSION

operation.

is not heard and there is

temperature.

pressure part of the

no frost.

compressor.

CAUSE

TEMPERATURE

OF THE

COMPRESSOR

REMARKS

STATE OF

THE UNIT

STATE OF THE

EVAPORATOR

LEAKAGE

RESTRICTED

BY
DUST

DEFECTIVE

COMPRESSION

Observe the discharging point of the refrigerant, which may be in the oil discharging part of the compressor and in a hole
in the evaporator.