Table 28. Limits for particulates and gases

Contaminant

Limits

Particulate

• The room air must be continuously filtered with 40% atmospheric dust spot efficiency

(MERV 9) according to ASHRAE Standard 52.2

1

.

• Air that enters a data center must be filtered to 99.97% efficiency or greater, using

high-efficiency particulate air (HEPA) filters that meet MIL-STD-282.

• The deliquescent relative humidity of the particulate contamination must be more than 60%

2

.

• The room must be free of conductive contamination such as zinc whiskers.

Gaseous

• Copper: Class G1 as per ANSI/ISA 71.04-1985

3

• Silver: Corrosion rate of less than 300 Å in 30 days

1

ASHRAE 52.2-2008 - Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle

Size. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

2

The deliquescent relative humidity of particulate contamination is the relative humidity at which the dust absorbs

enough water to become wet and promote ionic conduction.

3

ANSI/ISA-71.04-1985. Environmental conditions for process measurement and control systems: Airborne

contaminants. Instrument Society of America, Research Triangle Park, North Carolina, U.S.A.