Hid-dynavision dali son and cdo – Philips 220-230-240V User Manual

Page 113

Advertising
background image

OEM Catalogue 2009/2010

3.113

HID Gear

D1

A2

B1

B2

A3

A1

C1

HID-DV

Type

A1Nom

A2Nom

A3Nom

B1Nom

B2Nom

C1Nom

D1Nom

HID-DynaVision DALI

150.0

134.0

136.0

90.0

70.0

40.0

4.5

HID-DynaVision DALI SON and CDO

Inrush current

Type

Maximum

gear number

on MCB

(x)

Inrush

current

Peak

(A)

Inrush

current

Width

(ms)

HID-D DALI 100-150 /S CDO/SON/SDW

6

50

0.45

Electrical data

Type

Number

of

Lamps

(x)

Rated

Gear-

Lamp

Power

Line

Frequency

(Hz)

Line

Voltage

(V)

T-case

life

(ºC)

T-case

maximum

(ºC)

T-ambient

Ignition

Voltage

(kV)

Cable-Cap

outputwires

mutual

(pF)

HID-D DALI 100-150 /S CDO/SON/SDW

1

100-150

50/60

220-240

90

100

45

4.00

1000

Ordering and packing data

Type

EAN code

1 piece

Weight

Qty bulk

packing

Dimensions bulk packing

EAN code

bulk packing

EOC

8711500

HID-D DALI 100-150 /S CDO/SON/SDW

8711500928733

0.725 kg

10

39.8 cm x 16 cm x 11.1 cm

8711500928740

928733 30

Electrical installation notes

Mains operation
Rated mains voltage

220-240 V

With tolerances for performance
+6%-8%

203-254 V

With tolerances for operation

180-264 V

Mains frequency

50/60 Hz

Power factor 100% power

>0.98

Power factor 35% power

>0.93

Earth leakage current

<0.2 mA per driver

Overvoltage protection

48 hrs at 325 Vac
2 hrs at 366 Vac
5 min. at 400 Vac

Lamp operation
Operation frequency (typical)

125 Hz

Ignition voltage

3-4 kV

Cable capacity
SON-100-150W lamps (2.7 kV)

Max. 1 nF

CDO-lamps (3.3 kV)

Max. 0.5 nF

Air and creepage distance from any
(metal) part that may become live,
to earthed environment (class I) or
test finger (class II)

>4 mm

Notes:
1. With three-phase mains supply, neutral should never be
disconnected; otherwise circuitry could be damaged.
2. For proper EMC, wiring inside luminaire should be as straight and as
short as possible; mains wires should not run parallel to lamp wires.
3. Driver should be mounted in luminaire >min IP 23.
4. Thermo-protected circuit incorporates self-resetting facility; ignition
attempts stop after seven minutes; mains supply must be switched off
and on to reset driver.
5. Insulation resistance test: 500 Vdc from Line/Neutral to Earth (not
between Line and Neutral). Ensure that the Neutral is reconnected
again after abovementioned test is carried out and before the
installation is put into operation.