Hid-dynavision dali son and cdo – Philips 220-230-240V User Manual
Page 113

OEM Catalogue 2009/2010
3.113
HID Gear
D1
A2
B1
B2
A3
A1
C1
HID-DV
Type
A1Nom
A2Nom
A3Nom
B1Nom
B2Nom
C1Nom
D1Nom
HID-DynaVision DALI
150.0
134.0
136.0
90.0
70.0
40.0
4.5
HID-DynaVision DALI SON and CDO
Inrush current
Type
Maximum
gear number
on MCB
(x)
Inrush
current
Peak
(A)
Inrush
current
Width
(ms)
HID-D DALI 100-150 /S CDO/SON/SDW
6
50
0.45
Electrical data
Type
Number
of
Lamps
(x)
Rated
Gear-
Lamp
Power
Line
Frequency
(Hz)
Line
Voltage
(V)
T-case
life
(ºC)
T-case
maximum
(ºC)
T-ambient
Ignition
Voltage
(kV)
Cable-Cap
outputwires
mutual
(pF)
HID-D DALI 100-150 /S CDO/SON/SDW
1
100-150
50/60
220-240
90
100
45
4.00
1000
Ordering and packing data
Type
EAN code
1 piece
Weight
Qty bulk
packing
Dimensions bulk packing
EAN code
bulk packing
EOC
8711500
HID-D DALI 100-150 /S CDO/SON/SDW
8711500928733
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500928740
928733 30
Electrical installation notes
Mains operation
Rated mains voltage
220-240 V
With tolerances for performance
+6%-8%
203-254 V
With tolerances for operation
180-264 V
Mains frequency
50/60 Hz
Power factor 100% power
>0.98
Power factor 35% power
>0.93
Earth leakage current
<0.2 mA per driver
Overvoltage protection
48 hrs at 325 Vac
2 hrs at 366 Vac
5 min. at 400 Vac
Lamp operation
Operation frequency (typical)
125 Hz
Ignition voltage
3-4 kV
Cable capacity
SON-100-150W lamps (2.7 kV)
Max. 1 nF
CDO-lamps (3.3 kV)
Max. 0.5 nF
Air and creepage distance from any
(metal) part that may become live,
to earthed environment (class I) or
test finger (class II)
>4 mm
Notes:
1. With three-phase mains supply, neutral should never be
disconnected; otherwise circuitry could be damaged.
2. For proper EMC, wiring inside luminaire should be as straight and as
short as possible; mains wires should not run parallel to lamp wires.
3. Driver should be mounted in luminaire >min IP 23.
4. Thermo-protected circuit incorporates self-resetting facility; ignition
attempts stop after seven minutes; mains supply must be switched off
and on to reset driver.
5. Insulation resistance test: 500 Vdc from Line/Neutral to Earth (not
between Line and Neutral). Ensure that the Neutral is reconnected
again after abovementioned test is carried out and before the
installation is put into operation.