TROUBLESHOOTING – SERVICE TIPS

13. TROUBLESHOOTING – SERVICE TIPS

Problem

Possible Cause

Suggested Remedy

Defective Thermocouple

Replace

Heavy Draft Blowing across Pilot

Redirect Air Movement or Eliminate

Plugged Pilot Orifice

Replace Orifice

Pilot Outage

Check Manual Pilot Valve
Check Main Gas Shut-Off Valve

No Gas

Check Manual Meter Valve
Consult Gas Company

Defective Thermopilot Valve

Replace

Defective Ignition Control

Replace

No Power

Check Power Source with Meter
Check Fuses

Defective Gas Valve

Replace

Defective Thermocouple

Replace

Low Water Level in Boiler

Check for Leaks

Main Gas Valve Will Not Open

or System Causing Low Water Cut-off to Function

Check Feeder (if Supplied)

(Standard Spark-Ignited Pilot System)

Defective Thermopilot Valve

Replace

Defective Ignition Control

Replace

High Gas Pressure Switch Open

Check Switch Setting

(if Provided)

Check Manifold Gas Pressure

Low Gas Pressure Switch Open

Check Switch Setting

(if Provided)

Check Manifold Gas Pressure

No Power

Check Power Source with Meter
Check Fuses

Defective Gas Valve

Replace

Relay Locked Out on Safety

Check for Pilot Outage

Pilot Out

Relight Pilot
(May have defective pilot valve or relay)

Main Gas Valve Will Not Open

Defective Relay

Replace

(Electronic Standing Pilot System)

Low Water in Boiler

Check for Leaks

or System Causing Low Water Cut-off to Function

Check Feeder (if Supplied)

Defective Thermopilot Valve(s)

Replace

Defective Thermocouple(s)

Replace

High Gas Pressure Switch Open

Check Switch Setting

(if Provided)

Check Manifold Gas Pressure

Low Gas Pressure Switch Open

Check Switch Setting

(if Provided)

Check Inlet Gas Pressure

Air Adjustment Screws Turned in Too Far

Adjust Screws Out

Low Gas Pressure in Manifold

Adjust Main Gas Pressure Regulator

(Insufficient Air Injection)

or Check Line Pressure

Burner Ports Partially Closed (Rust, Dirt, Lint, etc.)

Replace Burners or Clean Ports

Burner(s) Burning with Yellow Flame

Check Size of Combustion Air Openings to

Insufficient Air for Combustion

Room, if Undersized, Correct as Required
Check for Negative Pressure in Boiler Room

Oversized Burner Orifice

Install Correct Orifice

High Gas Pressure in Manifold

Adjust Main Gas Pressure Regulator

Insufficient Draft – Chimney Too Low

Increase Height or Add Induced Draft Fan

Insufficient Draft – Chimney Too Small

Replace Chimney or Add Induced Draft Fan

Gas Spillage from

Insufficient Draft – Blockage in Chimney or Vent

Repair Chimney or Vent

Insufficient Draft – Downdraft Caused by

Draft Hood Relief Opening

Chimney Location with Respect to

Install Chimney Cap

Other Buildings, Roofs, etc.

Negative Pressure in Boiler Room

Remove Exhaust Fan

(Due to Exhaust Fan or Duct System)

or Isolate Fan From Boiler Room

Insufficient Combustion Air Openings

Provide Correctly Sized Combustion and
Ventilation Air Openings