8.2.2.3. Anti-Freezing Control

1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.

2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.

3. At the same time, indoor fan speed increase +40 rpm compared to its normal operation.

4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.

8.2.2.4. Anti-Dew Formation Control

a) Control 1

• During anti-dew formation control, compressor operates at frequency shift as shown below when indoor fan speed is less

than Me.

• This control is cancelled after started for 420 minutes, or remote control setting temperature or fan speed setting is changed.

b) Control 2

• When the following conditions occurs for 20 minutes continuously, anti-dew formation is controlled and air vane change

Horizontal vane shift to 2nd position and Vertical vane shift to center position.

1. Indoor intake air temperature is 25°C or above and less than 29°C.

2. Outdoor air temperature is less than 30°C.

3. Air vane control: Manual Horizontal Airflow and Manual Vertical Airflow.

4. Fan speed is quiet Lo.