R410a tools – Panasonic CS-E21CKE User Manual

Page 54

Advertising
background image

10.2.2. R410A Tools

1. Cooper tube gauge for clearance adjustment

(used when flaring with the conventional flaring tool (clutch
type))

• This gauge makes it easy to set the clearance for the

copper tube to 1.0-1.5 mm from the clamp bar of the
flaring tool.

2. Flaring tool (clutch type)

• In the R410A flaring tool, the receiving hole for the

clamp bar is enlarged so the clearance from the clamp
bar can be set to 0-0.5 mm, and the spring inside the
tool is strengthened to increase the strength of the pipe-
expanding torque. This flaring tools can also be used
with R22 piping, so we recommend that you select it if
you are buying a new flaring tool.

3. Torque wrenches

4. Manifold gauge

Fig. 1 Copper tube gauge for clearance adjustment

Fig. 2 Flaring tool (clutch type)

Fig. 3 Torque wrenches

Table 5

Conventional wrenches

R410A wrenches

For 1/4 (opposite side x torque)

17 mm x 18 N.m (180 kgf.cm)

17 mm x 18 N.m (180 kgf.cm)

For 3/3 (opposite side x torque)

22 mm x 42 N.m (180 kgf.cm)

22 mm x 42 N.m (180 kgf.cm)

For 1/2 (opposite side x torque)

24 mm x 55 N.m (180 kgf.cm)

26 mm x 55 N.m (180 kgf.cm)

• Because the pressure is higher for the R410A type, the conventional type cannot be used.

Table 6 Difference between R410A and conventional high / low-pressure gauges

Conventional wrenches

R410A wrenches

High-pressure gauge (red)

-76 cmHg - 35 kgf/cm

3

-0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm

3

High-pressure gauge (blue)

-76 cmHg - 17 kgf/cm

3

-0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm

3

• The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of

refrigerant.

Table 7 Difference between R410A and conventional manifold port size

Conventional gauges

R410A gauges

Port size

7/6 UNF 20 threads