8.4. Operation Control

8.4.1. Restart Control (Time Delay Safety Control)

When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-

Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.

Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.

If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.

This phenomenon is to balance the pressure inside the refrigerant cycle.

8.4.2. 7 Minutes Time Save Control

The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.

This phenomenon is to reduce the built up humidity inside a room.

8.4.3. 60 Seconds Forced Operation

Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.

The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.

8.4.4. Starting Current Control

When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.

The reason of the difference is to reduce the starting current flow.