11.5. Evacuation

(No refrigerant in the refrigeration cycle)

Procedure:
1. Connect the vacuum pump to the charge set’s centre

hose.

2. Evacuation for approximately one hour.

•

Confirm that the gauge needle has moved toward -14.5
PSI (-76 cmHg) [vacuum of 4 mmHg or less.]

3. Close the valve (Low side) on the charge set, turn off

the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning
off the vacuum pump).

4. Disconnect the charge hose from the vacuum pump.

•

Vacuum pump oil
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.