Airflow direction, Vertical airflow – Philips CS-E15DB4EW User Manual

Page 24

Advertising
background image

8.1.8. Airflow Direction

1. There are one types of airflow, vertical airflow (directed by horizontal vane).

2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature

and intake air temperature) and manual (angles of direction can be adjusted using remote control).

8.1.8.1. Vertical Airflow

Operation Mode

Airflow Direction

Vane Angle (°)

1

2

3

4

5

Heating

Auto with Heat Exchanger

A

Downward fix

70

Temperature

B

Downward fix

70

C

Upward fix

20

D

Upward fix

20

Manual

20

-

-

-

70

Cooling, Soft Dry and Ion

Auto

20 ~ 70

Manual

20

-

-

-

70

1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated

above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.

2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions

of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

8.1.9. Quiet operation (Cooling Mode/Cooling area of Dry Mode)

A. Purpose

To provide quiet cooling operation compare to normal operation.

B. Control condition

a. Quiet operation start condition

• When “quiet” button at remote control is pressed.

Quiet LED illuminates.

b. Quiet operation stop condition

1. When one of the following conditions is satisfied, quiet operation stops:

a. Powerful button is pressed.

b. Stop by OFF/ON switch.

c.

Timer “off” activates.

d. Quiet button is pressed again.

2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.

3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.

5. During quiet operation, if timer “on” activates, quiet operation maintains.

6. After off, when on back, quiet operation is not memorised.

24