INSTALLATION

OUTDOORS: Choose a location where the

generator will not be exposed to rain, snow or direct
sunlight. Position the generator on secure, level
ground so it will not tip or slide down a hill. Place the
generator so that the exhaust fumes will not be
directed towards people.

The installation site must be free from water,

moisture, or dust. All electrical components should be
protected from excessive moisture or the insulation
sy stem will deteriorate and result in grounding or
shorting out the generating system.

Foreign matters, such as dust, dirt, sand, lint, or

abrasive materials can cause damage to the generator
head and engine if allowed into its cooling system.

NEVER install your generator inside confined

areas. Inside installation can cause health hazards or
death.

DANGER

Remember, exhaust fumes are

deadly carbon monoxide gas, and must be vented to
the outside where there are no people. Cooling air of
sufficient amounts must be allowed to flow in and
exhausted out to ensure proper cooling of the engine
and generator head.

LOAD APPLICATION

It is important to determine the total electrical load

before it is connected to the generator. The two major
factors in determining the life of a generator head are:
heat build up, caused by overloading the generator;
and corrosive contaminants that attack the wiring
insulation. If the generator is overloaded, the wires
become excessively hot and cause the insulation to
break down, reducing its ability to resist corrosive
contaminants. Over time the effectiveness of the
insulation is eliminated and a dead short can result.

Always compare the generator nameplate data

with that of the equipment to be used to ensure that
watts, volts, amperage, and frequency requirements
are suitable for operating equipment. The wattage
listed on the equipment nameplate is its rated output.
However, some equipment may require three to ten
times more wattage than its rating on the nameplate,
as the wattage is influenced by the equipment
efficiency, power factor and starting system. NOTE: If
wattage is not given on equipment nameplate,
approximate wattage may be determined by
multiplying nameplate voltage by nameplate
amperage.

VOLTS X AMPS = WATTS
Example: 120V X 5A

= 600W

When connecting a resistive load such as

incandescent lights, heaters or common electric power

tools, a capacity of up to the generator full rated
wattage output can be used.

When connecting a resistive-inductive load such

as a fluorescent or mercury light, transformers or
inductive coils, a capacity of up to 0.6 times the
generator’s full rated output can be used.

Always allow the generator to reach operating

speed before a load is applied.

STARTING ELECTRIC MOTORS

Electric motors require much more current (amps)

to start than to run. Some motors, particularly low cost
split-phase motors, are very hard to start and require 5
to 7 times more current to start than to run. Capacitor
motors are easier to start and usually require 2 to 4
times as much current to start as to run. Repulsion
Induction motors are the easiest to start and require
1.5 to 2.5 times as much to start as to run.

Most fractional motors take about the same

amount of current to run them whether they are of
Repulsion-Induction (RI), Capacitor (Cap), or Split-
Phase (SP) type. The following chart shows the
approximate current required to start and run various
types and sizes of 120 volt 60 cycle electric motors
under various conditions.

120V, 60 Hz Motors

Starting Amps

Hp motor

Running

Watts

RI type

Cap type

SP type

1/6

525

7-11

9-18

16-22

1/4

700

9-15

12-23

22-32

1/3

875

11-18

14-29

26-35

1/2

1175

15-25

20-40

NA

1

1925

24-40

32-64

NA

1 1/2

2400

30-50

40-80

NA

2

2900

36-60

48-96

NA

3

4075

51-85

68-136

NA

5

6750

84-140

112-224

NA

The figures given above are for an average load

such as a blower or fan. If the electric motor is
connected to a hard starting load, such as an air
compressor, it will require more starting current. If it is
connected to a light load, such as a power saw, it will
require less starting current. The exact requirement
will also vary with the brand or design of the motor.

Generators respond to severe overloading

differently than the power line. When overloaded, the
engine is not able to supply enough power to bring the
electric motor up to operating speed. The generator
responds to the high initial starting current, but the
engine speed drops sharply. The overload may stall
the engine. If allowed to operate at very low speeds,
the electric motor starting winding will burn out in a
short time. The generator head winding might also be
damaged.