Operation instructions, Continuous operation, Internittent operation – Lifebreath 2500EFD User Manual

Page 7: Optional remote controls, Installation tips

Advertising
background image

7

Operation Instructions

The LIFEBREATH 2500 series HRV is designed
tobe operated continuously or intermittently to meet
the requirements of the application.

Continuous Operation

For continuous operation, a simple jumper across
the ON/OFF and COMMON jumper terminals is
needed. HIGH/LOW speed selection requires
another jumper across HIGH/LOW and COMMON;
select as required (see below and wiring diagram).

Internittent Operation

Due to variance in the times in which buildings are
occupied and equipment or machinery operated,
inter mittent ventilation may be the preferred
method.

Dry contacts located inside the electrical panel
enable this unit to turn ON and OFF, and/or jump
between HIGH and LOW speeds when optional low
voltage controls are connected (see above and
pg. 9).

Optional Remote Controls

Basic controls such as dehumidistats, mechanical
crank timers, 24-hour timers or toggle switches can
be used to control the unit (see pg. 9).

Installation Tips

1. Whichever method is chosen to operate the

2500, keep in mind that Air-to Air exchangers
in general are not "booster fans" and are
normally sized to ventilate at a steady rate.

To achieve optimum performance from the

2500, the desired ventilation rate (speed of
the system) should be reached before the

contaminant to be removed has reached
its maximum.

EXAMPLE: A bingo hall opening at 7:00PM that is
sized for 5000 cfm should have at least this amount
of air exchange by that time. If the unit is not turned
on or set to its designated speed until after the con-
taminant has reached an uncomfortable level, then
it may result in a number of hours
passing before the system could catch up.

2. It is highly recommended that back draft

dampers be installed in the supply and
exhaust duct work to the outside, to prevent
air from entering in through the HRV when the
unit is off. Failure to install back draft
dampers may result in damage to HVAC
equipment and/or other building components.

ON/OFF

Low Voltage-24VAC

HIGH/LOW

T3 -

On/Off

T2 -

High/Low

T1 -

Common

Advertising