Optional remote controls, User adjustable defrost, Operation – Lifebreath 2500EFD User Manual

Page 8: Defrost off, Examples of defrost cycles, Supplied and installed by contractor, 15 hr. (10 mins), 50 hr. (30 mins)

Advertising
background image

8

Off

10

20

30

40

50

60

DEHUMID

ISTAT

Optional Remote Controls

ON

OFF

HIGH

LOW

Supplied
and Installed
by Contractor

Dehum

idistat

Setting

Relativ

e to

Outside

Condit

ions

WINTER

:

Set deh

umidist

at

betwee

n 30% t

o 40%.

If home

is too d

ry,

adjust t

o highe

r settin

g.

If home

is too h

umid,

adjust t

o lower

setting

.

SUMME

R:

Set deh

umidist

at

to OFF.

User Adjustable Defrost

DEHUMIDISTAT VENTILATION CONTROL*

LOCATION: Spa or pool area, anywhere that humidity

is a concern. (connect 1/unit only)

• Ventilation control turns HRV system OFF and ON.
• Dehumidistat increases ventilation when required
• High speed override switch
Red - common / Black - hi/low / Orange - on/off
PART NO. 99-116 c/w 3 wire cable 60' (18m)

REMOTE DEHUMIDISTAT
LOCATION:
Spa or pool area, anywhere that humidity

is a concern.

• Provides high speed ventilation when humidity level

exceeds selected setting.

PART NO. 99-130

CRANK TIMER
Provides high speed ventilation as required.
Crank Timer - 60 minute
PART NO. 99-101

ON/OFF

HIGH/LOW

COMMON

I

I

I

I

I

I

I

I

I

I

I

I

I

I

II

II

II

II

II

II

II

II

II

II

I

I

I

I

I

I

I

I

I

I

I

I

I

I

ON

OFF

hrs

0

0.2

0.4

0.6

0.8

1.0

Factory pre-set dial positions

DO NOT ADJUST

Defrost timer device

(see wiring diagram
for location)

Yellow (outer dial)
adjusts length of time
between defrost cycles
(OFF cycle)

Orange (center dial)
adjusts time spent in
defrost mode
(ON cycle)

Orange

Yellow

ON

OFF

OPERATION

Once the snap disk senses temperatures below
-3˚C (27˚F), it will activate the defrost mode,
which begins with the Defrost OFF cycle, and
then continues into the Defrost ON cycle.

Factory pre-set defrost
cycle and time are:

DEFROST ON

=.15 HR. (10 mins)

DEFROST OFF

=.50 HR. (30 mins)

32ºF (0ºC)

No defrost required

13ºF (-11ºC)

10 mins. defrost ON - 30 mins. defrost OFF

-40ºF (-40ºC)

15 mins. defrost ON - 30 mins. defrost OFF

EXAMPLES OF DEFROST CYCLES