Nordyne E3 Series User Manual

Page 13

Advertising
background image

13

Figure 9. Platinum Duct Connector

Mounting Plate

Duct

Connector

Secure Duct Connector and Mounting
Plate with 2 Flat-Head Screws or Nails

14" Supply Connection

Method D
1.

Score and cut top of metal duct as indicated
in Figure 12, Step 1 or Step 2. If using Step
1, also cut out metal from the shaded area
“A”.

2. Fold the duct fl ap “B” up (see Figure 12,

Step 3).

3.

At the front-to-back of duct run (see Figure
12, area “A”), bend the duct connector tabs
and secure them directly to the duct.

4.

At area “B”, bend the duct connector tabs up
and back over, around the duct connector
(see Figure 12, step 3).

Figure 10. Duct Connector Installation B

5. Fold/form the duct fl ap against the side of

the duct connector and attach as shown
(see Figure 12, Step 4). Use at least three
staples on each duct fl ap OR... if a 2X
block/joist is not provided, use at least two
sheet metal fasteners on each duct fl ap.

6.

Seal the duct fl ap edges with an approved
tape or compound for a leak-free joint.

Method E
1. Apply a bead of caulking, mastic, or other

approved sealant around bottom side of
1/2” fl ange and restrictor plate, when ap-
plicable.

TABS

DUCT

1. INSERT DUCT CONNECTOR

INTO DUCT CUT-OUT

TABS

DUCT

2. BEND BOTTOM TABS OVER

AND ONTO THE UNDER-

NEATH DUCT SURFACE

Advertising
This manual is related to the following products: